15

Subcooling = Saturated Line Temperature - Liquid Line Temperature

Single Speed Application—WPC45

1.

Purge the gauge lines. 

2.

Connect the service gauge manifold to the access fittings. 
Run the system for at least 10 minutes to allow the pressure 
to stabilize.

3.

Temporarily install a thermometer on the liquid (small) line 
near the liquid line access fitting with adequate contact and 
insulate for best possible reading.

4.

Check subcooling and superheat. Systems with TXV 
application should have a subcooling of 10 + 2°F and 
superheat of 15ºF to 18ºF.

a)

If subcooling and superheat are low, adjust TXV to 15ºF to 
18ºF, and then check subcooling.

b)

If subcooling is low and superheat is high, add charge to 
raise subcooling to 10ºF ± 2ºF then check superheat.

c)

If subcooling and superheat are high, adjust TXV valve to 
15ºF to 18ºF, and then check subcooling.

d)

If subcooling is high and superheat is low, adjust TXV 
valve to 15ºG to 18ºF superheat and remove charge to 
lower the subcooling to 10ºF ± 2ºF.

NOTES: 

The TXV should not be adjusted at light load conditions of 
55ºF (13ºC) to 60ºF (16ºC). Under such conditions, only the 
subcooling can be evaluated. This is because the suction 
pressure is dependent upon the indoor airflow and the wet 
bulb temperature.

Do not adjust the charge based on the suction pressure 
unless there is a gross undercharge.

5.

Disconnect the manifold set. Installation is complete.

2-Speed Application—WGPH45

Run the unit on low-stage cooling for 10 minutes until the 
refrigerant pressures stabilize. Follow the guidelines and methods 
below to check the unit operation and ensure that the refrigerant 
charge is within limits. Charge the unit on low stage.

1.

Purge the gauge lines. 

2.

Connect the service gauge manifold to the access fittings. 
Run the system for at least 10 minutes to allow the pressure 
to stabilize.

3.

Temporarily install a thermometer on the liquid (small) line 
near the liquid line access fitting with adequate contact and 
insulate for best possible reading.

4.

Check subcooling and superheat. The 2-stage systems 
running on low stage with TXV application should have a 
subcooling of 5ºF to 7ºF and superheat of 15ºF to 18ºF.

a)

If subcooling and superheat are low, adjust TXV to 15ºF to 
18ºF superheat, then check subcooling.

NOTE:

 To adjust superheat, turn the valve stem clockwise 

to increase and counterclockwise to decrease.

b)

If subcooling is low and superheat is high, add charge to 
raise subcooling to 5ºF to 7ºF, and then check superheat.

c)

If subcooling and superheat are high, adjust TXV valve to 
15ºF to 18ºF superheat, and then check subcooling.

d)

If subcooling is high and superheat is low, adjust TXV 
valve to 15ºF to 18ºF superheat and remove charge to 
lower the subcooling to 5ºF to 7ºF.

NOTE:

 Do not adjust the charge based on the suction 

pressure unless there is a gross undercharge.

5.

Disconnect the manifold set. Installation is complete.

70

15 150

53 

72

16

160

56 

74

17 170

60 

76

19 

Saturated Liquid Pressure Temperature

Liquid Pressure

Saturated Liquid Temperature ºF

Liquid Pressure

Saturated Liquid Temperature ºF

PSIG

R-410A

PSIG

R-410A

200

70 375

112 

210

73 405

118 

220

76 415

119 

225

78 425

121 

235

80 435

123 

245

83 445

125 

255

85 475

130 

265

88 500

134 

275

90 525

138 

285

92 550

142 

295

95 575

145 

305

97 600

149 

325

101 625

152 

355

108 

Saturated Suction Pressure Temperature

Suction Pressure

Saturated Suction Temperature ºF 

Suction Pressure

Saturated Suction Temperature ºF 

PSIG

R-410A

PSIG

R-410A

Содержание Gold WGPH45**AM

Страница 1: ...ectric Heat Installation and Adjustment 6 Make Electrical Connections 6 Complete Installation 7 SEQUENCE OF OPERATION 7 Start up Procedure Cooling Cycle 7 Start up Procedure Heat Pump 8 Final System Checks 8 Explanation and Guidance Heat Pump 8 Defrost Cycle 9 System Troubleshooting 10 Circulating Air Blower 11 Blower Performance Data 12 CHARGE VERIFICATION 14 SYSTEM MAINTENANCE 16 TROUBLESHOOTING...

Страница 2: ...e unit be placed so that the condenser air discharge does not blow toward windows less than 25 ft 7 6 m away Heat pumps require special location consideration in areas of heavy snow accumulation and or areas with prolonged continuous subfreezing temperatures Heat pump unit bases have holes under the outdoor coil to permit drainage of defrost water accumulation The unit must be situated to allow fr...

Страница 3: ...g and general roofing material are furnished by the contractor Curbing must be installed in compliance with the National Roofing Contractors Association Manual Construct ductwork using current industry guidelines The ductwork must be placed into the roof curb before mounting the package unit Minimum Clearances The unit is designed to be located outside the building with an unobstructed condenser a...

Страница 4: ... outdoor use Use copper conductors only All field wiring must be done in accordance with National Electrical Code requirements applicable requirements of UL or local codes where applicable Electrical wiring disconnect means and over current protection are to be supplied by the installer Refer to the rating plate for the maximum over current protection minimum service ampacity and operating voltage...

Страница 5: ... and must be supplied and installed in the return duct system by the installer A field installed filter grille is recommended for easy and convenient access to the filters for periodic inspection and cleaning Filters must have adequate face area for the rated quantity of the unit See the Air Delivery Table for the recommended filter size Air Delivery Table Goodman 109 To prevent property damage th...

Страница 6: ... of larger size than indicated could result in extensive damage to the equipment The manufacturer bears no responsibility for damage caused to equipment as result of the use of larger than is recommended size protective devices All units have undergone a run test prior to packaging for shipment This equipment has been started at minimum rated voltage and checked for satisfactory operation Do not a...

Страница 7: ...2 Dispose of recycle all packaging materials 3 Check the heat pump or condensing unit in its final location SEQUENCE OF OPERATION Start upProcedure CoolingCycle 1 Disconnect power 2 Turn the thermostat switch to Cool and the fan switch to Auto 3 Set the temperature setting to the highest setting 4 Verify that all of the registers are set to the normal open position 5 Turn on the electrical supply ...

Страница 8: ...s free from excessive vibration 4 Check that the tubes and lines are not rubbing against each other or against the sheet metal surfaces or edges If contact is found correct the problem 5 Set the thermostat at the appropriate setting for cooling and heating or automatic changeover for normal use 6 Check that the owner is instructed on the unit operation filter servicing correct thermostat operation...

Страница 9: ...d the unit s defrost cycle will be initiated provided the sensor remains closed When the sensor opens approximately 60 F 16ºC the defrost cycle is terminated and the timing period is reset If the defrost cycle is not terminated due to the sensor temperature a 10 minute override interrupts the unit s defrost period Circuit Board Suggested Field Testing Troubleshooting 1 Run the unit in the heating ...

Страница 10: ...citor weak open or shorted Check for unit voltage at compressor Check and tighten all connections Wait at least 2 hours for overload to reset If still open replace the compressor At compressor terminals voltage must be within 10 of nameplate volts when unit is operating Check capacitor Replace if defective Low suction Cool compressor iced evaporator coil Low indoor airflow Increase speed of blower...

Страница 11: ... be changed according to the electric heat size The ECM motor provides many features not available on the traditional PSC motor These features include Improved Efficiency Constant CFM Soft Start and Stop Improved Humidity Control ECM Motor Speed Adjustment Each ECM blower motor has been preprogrammed for operation at 4 distinct airflow levels when operating in Cooling Heat Pump mode or Electric He...

Страница 12: ... 889 819 Watts 202 214 221 229 235 246 258 264 T4 T5 CFM 1 267 1 213 1 162 1 120 1 058 1 009 932 841 Watts 218 226 236 245 247 260 272 275 WPC4542AM T1 CFM 1 123 1 070 1 025 984 942 894 839 774 Watts 162 170 182 193 204 216 229 242 T2 T3 CFM 1 437 1 390 1 354 1 318 1 281 1 243 1 204 1 165 Watts 310 317 331 342 355 366 377 389 T4 T5 CFM 1 528 1 490 1 450 1 410 1 383 1 348 1 312 1 267 Watts 372 379 ...

Страница 13: ... 1 700 B Plus 1 870 B Plus 1 870 A Minus 1 620 A Minus 1 620 A Normal 1 800 A Normal 1 800 A Plus 1 980 A Plus 1 980 WGPH4560AM Cooling HP Speed Adjust Tap CFM Electric Heat Adjust Tap CFM D Minus 1 260 D Minus 1 260 D Normal 1 400 D Normal 1 400 D Plus 1 540 D Plus 1 540 C Minus 1 440 C Minus 1 440 C Normal 1 600 C Normal 1 600 C Plus 1 760 C Plus 1 760 B Minus 1 620 B Minus 1 620 B Normal 1 800 ...

Страница 14: ...n 800 CFM Output for DIP Switch Combinations 5 and 6 Cooling Heating Model Speed Tap Switch 5 Switch 6 Cooling HP CFM WGPH4543 A Off Off 1 800 B On Off 1 700 C Off On 1 400 F D On On 1 225 WGPH4549 A Off Off 1 800 B On Off 1 700 C Off On 1 400 D On On 1 225 F WGPH4560 A Off Off 2 000 F B On Off 1 800 C Off On 1 600 D On On 1 400 DIP Switch Settings for Single and 2 Stage Thermostats Model Switch 3...

Страница 15: ...ithin limits Charge the unit on low stage 1 Purge the gauge lines 2 Connect the service gauge manifold to the access fittings Run the system for at least 10 minutes to allow the pressure to stabilize 3 Temporarily install a thermometer on the liquid small line near the liquid line access fitting with adequate contact and insulate for best possible reading 4 Check subcooling and superheat The 2 sta...

Страница 16: ... The return air filter must always be clean and sufficient air volume must pass through the indoor coil to prevent excessive discharge pressure and high pressure cutout Outside Air Into Return Duct Do not introduce cold outside air into the return duct of a heat pump installation Do not allow air entering the indoor coil to drop below 65 F 18ºC Air below this temperature will cause low discharge p...

Страница 17: ...V 208 TR C BK 1 R COMP CM BR 4 1 PLF BK Y S BK R 5 6 2 3 C R R O C W2 W1 G a t o t s m r e h T T2 T1 BU NOTE 2 PR L1 BU GND C L2 PR BK 60 1 0 4 2 8 0 2 7 8 9 BU BR W R R BK BK R Y BU BU R R DFT RVC LPS L 3 1 2 DC DFT DFT Y C R W2 O W1 Y1 G COM 4 5 6 PLF LVDR R R O O W2 HPS C If Used N G RVC See NOTE 4 SA If Used See NOTE 3 R Y BK BK BK OR OR W HPS Y BU BU BU BU Y Y LPS YCON OT2OT1 OTC O W W2 E W1 ...

Страница 18: ...K R 5 6 2 3 C R R O C W2 W1 G Y1 a t o t s m r e h T T2 T1 BU NOTE 2 PR L1 BU GND C L2 PR BK 60 1 0 4 2 8 0 2 7 8 9 BU BR W R R BK BK R Y BU BU R R DFT RVC LPS L 3 1 2 DC DFT DFT Y C R W2 O W1 Y1 G COM 4 5 6 PLF LVDR R R O O W2 HPS C If Used N G RVC See NOTE 4 SA If Used See NOTE 3 R Y BK BK BK OR OR W HPS Y BU BU Y BU BU Y Y LPS SOL BU Y BU YCON S0L OT2OT1 OTC O W W2 E W1 R YCON C OMO W2 ED OU TD...

Страница 19: ...A S T1 R L1 C NOTE 4 H F RCCF CM T2 C L2 Box H RCCF F C Y BR PR 2 24V 208 TR C BK 1 PR COMP CM BR BR PR 4 1 PLF PR BK Y S BK R BK 5 6 2 3 C R LVJB R BU BR W G Y R C W2 W1 G Y a t o t s m r e h T T2 T1 R BU NOTE 3 PR BU L1 GND C L2 PR BK 60 1 0 4 2 8 0 2 7 8 9 BU BR R R BK BK R C L G N 1 2 3 BU BU R G G G R EM G See NOTE 2 1 L 3 1 2 R W2 W1 Y G C 4 5 6 PLF EM 1 C See NOTE 2 If Used Thermostat N G 2...

Страница 20: ...time phone number in your correspondence Accessories To order accessories contact your Whirlpool Home Cooling and Heating dealer WPIO 362 2010 All rights reserved Registered Trademark TM Trademark of Whirlpool U S A Manufactured under license by Tradewinds Distributing Company LLC Jacksonville Florida Warranty provided by manufacturer All other trademarks are owned by their respective companies 2 ...

Отзывы: