background image

5

Place Heat Pump or Air Conditioning Unit in 

Final Location

IMPORTANT: 

If you are using a bottom discharge with the roof 

curb, the ductwork should be attached to the curb prior to the 
installation of the unit.

Lower the unit carefully onto the roof mounting curb. While you 
are rigging the unit, the center of gravity will cause the condenser 
end of the unit to be lower than the supply air end.

Rigging

Connect Condensate Drain

The condensate drain connection of the evaporator is a half 
coupling of 

³⁄₄

" N.P.T. A 

³⁄₄

" drain line with trap must be installed 

on all applications to avoid accumulation of condensate.

Condensate Drain Connection

Install the condensate drain trap as shown. Use a 

³⁄₄

" (1.9 cm) 

NPT drain connection size or larger.

An external trap must be installed for proper condensate 
drainage. 

Unit must be level or slightly inclined toward drain.

Install Ductwork

IMPORTANT:

 

Install ductwork in accordance with NFPA 90B and any local 
codes.

When the unit is installed so that the supply ducts carry air 
circulated by the unit to areas outside the space containing 
the unit, the return air shall be handled by a duct or ducts 
sealed to the unit casing and terminated outsides the space 
containing the unit.

If there is no complete return air duct system, the return air 
connection must be sealed to the unit casing and run full size 
to a location outside the utility room or space housing the unit 
to avoid a negative pressure on the venting system.

Filters

Filters are not provided with unit, and must be supplied and 
installed in the return duct system by the installer. A field installed 
filter grille is recommended for easy and convenient access to 
the filters for periodic inspection and cleaning. Filters must have 
adequate face area for the rated quantity of the unit. See the Air 
Delivery Table for the recommended filter size.

Air Delivery Table

Goodman 109

To prevent property damage, the unit should remain in
an upright position during all rigging and moving
operations. To facilitate lifting and moving when a crane
is used, place the unit in an adequate cable sling.

WARNING

Goodman 110

To prevent property damage, personal injury or death, 
ensure the roof has sufficient structural strength to carry 
the weight of the unit(s), roof curb, snow loads and water 
loads as required by local codes. Consult a structural 
engineer to determine the weight capabilities of the roof.

WARNING

Goodman 111

To avoid possible personal injury, a safe, flat surface for 
service personnel should be provided.

CAUTION

Placeholder for Rigging art

A. Drain connection
B. 2" (5.1 cm) minimum

C. 3" (7.6 cm) minimum

D. Positive liquid seal (required) 

E. Flexible tubing, hose or pipe

F. Unit

Minimum Filter Size

Nominal Size—in. (cm)

Nominal Area—sq ft (cm

2

)

10 x 20 (25.4 x 50.8)

1.4 (1,301)

14 x 20 (35.6 x 50.8)

1.9 (1,765)

14 x 25 (35.6 x 63.5)

2.4 (2,230)

15 x 20 (38.1 x 50.8)

2.1 (1,951)

16 x 20 (40.6 x 50.8)

2.2 (2,044)

16 x 25 (40.6 x 63.5)

2.8 (2,601)

20 x 20 (50.8 x 50.8)

2.8 (2,601)

20 x 25 (50.8 x 63.5)

3.5 (3,252)

25 x 25 (63.5 x 63.5)

4.3 (3,995)

A

F

B

E

C

D

500   1,000    1,500   2,000 2,500

3,000    3,500

7

(6,503)

Disposable Filter

Permanent Filter

Nominal Filter Area

sq ft (cm

2

)

6

(5,574)

5

(4,645)

4

(3,716)

3

(2,787)

2

(1,858)

Airflow - SCFM

Содержание Gold WGPH45**AM

Страница 1: ...ectric Heat Installation and Adjustment 6 Make Electrical Connections 6 Complete Installation 7 SEQUENCE OF OPERATION 7 Start up Procedure Cooling Cycle 7 Start up Procedure Heat Pump 8 Final System Checks 8 Explanation and Guidance Heat Pump 8 Defrost Cycle 9 System Troubleshooting 10 Circulating Air Blower 11 Blower Performance Data 12 CHARGE VERIFICATION 14 SYSTEM MAINTENANCE 16 TROUBLESHOOTING...

Страница 2: ...e unit be placed so that the condenser air discharge does not blow toward windows less than 25 ft 7 6 m away Heat pumps require special location consideration in areas of heavy snow accumulation and or areas with prolonged continuous subfreezing temperatures Heat pump unit bases have holes under the outdoor coil to permit drainage of defrost water accumulation The unit must be situated to allow fr...

Страница 3: ...g and general roofing material are furnished by the contractor Curbing must be installed in compliance with the National Roofing Contractors Association Manual Construct ductwork using current industry guidelines The ductwork must be placed into the roof curb before mounting the package unit Minimum Clearances The unit is designed to be located outside the building with an unobstructed condenser a...

Страница 4: ... outdoor use Use copper conductors only All field wiring must be done in accordance with National Electrical Code requirements applicable requirements of UL or local codes where applicable Electrical wiring disconnect means and over current protection are to be supplied by the installer Refer to the rating plate for the maximum over current protection minimum service ampacity and operating voltage...

Страница 5: ... and must be supplied and installed in the return duct system by the installer A field installed filter grille is recommended for easy and convenient access to the filters for periodic inspection and cleaning Filters must have adequate face area for the rated quantity of the unit See the Air Delivery Table for the recommended filter size Air Delivery Table Goodman 109 To prevent property damage th...

Страница 6: ... of larger size than indicated could result in extensive damage to the equipment The manufacturer bears no responsibility for damage caused to equipment as result of the use of larger than is recommended size protective devices All units have undergone a run test prior to packaging for shipment This equipment has been started at minimum rated voltage and checked for satisfactory operation Do not a...

Страница 7: ...2 Dispose of recycle all packaging materials 3 Check the heat pump or condensing unit in its final location SEQUENCE OF OPERATION Start upProcedure CoolingCycle 1 Disconnect power 2 Turn the thermostat switch to Cool and the fan switch to Auto 3 Set the temperature setting to the highest setting 4 Verify that all of the registers are set to the normal open position 5 Turn on the electrical supply ...

Страница 8: ...s free from excessive vibration 4 Check that the tubes and lines are not rubbing against each other or against the sheet metal surfaces or edges If contact is found correct the problem 5 Set the thermostat at the appropriate setting for cooling and heating or automatic changeover for normal use 6 Check that the owner is instructed on the unit operation filter servicing correct thermostat operation...

Страница 9: ...d the unit s defrost cycle will be initiated provided the sensor remains closed When the sensor opens approximately 60 F 16ºC the defrost cycle is terminated and the timing period is reset If the defrost cycle is not terminated due to the sensor temperature a 10 minute override interrupts the unit s defrost period Circuit Board Suggested Field Testing Troubleshooting 1 Run the unit in the heating ...

Страница 10: ...citor weak open or shorted Check for unit voltage at compressor Check and tighten all connections Wait at least 2 hours for overload to reset If still open replace the compressor At compressor terminals voltage must be within 10 of nameplate volts when unit is operating Check capacitor Replace if defective Low suction Cool compressor iced evaporator coil Low indoor airflow Increase speed of blower...

Страница 11: ... be changed according to the electric heat size The ECM motor provides many features not available on the traditional PSC motor These features include Improved Efficiency Constant CFM Soft Start and Stop Improved Humidity Control ECM Motor Speed Adjustment Each ECM blower motor has been preprogrammed for operation at 4 distinct airflow levels when operating in Cooling Heat Pump mode or Electric He...

Страница 12: ... 889 819 Watts 202 214 221 229 235 246 258 264 T4 T5 CFM 1 267 1 213 1 162 1 120 1 058 1 009 932 841 Watts 218 226 236 245 247 260 272 275 WPC4542AM T1 CFM 1 123 1 070 1 025 984 942 894 839 774 Watts 162 170 182 193 204 216 229 242 T2 T3 CFM 1 437 1 390 1 354 1 318 1 281 1 243 1 204 1 165 Watts 310 317 331 342 355 366 377 389 T4 T5 CFM 1 528 1 490 1 450 1 410 1 383 1 348 1 312 1 267 Watts 372 379 ...

Страница 13: ... 1 700 B Plus 1 870 B Plus 1 870 A Minus 1 620 A Minus 1 620 A Normal 1 800 A Normal 1 800 A Plus 1 980 A Plus 1 980 WGPH4560AM Cooling HP Speed Adjust Tap CFM Electric Heat Adjust Tap CFM D Minus 1 260 D Minus 1 260 D Normal 1 400 D Normal 1 400 D Plus 1 540 D Plus 1 540 C Minus 1 440 C Minus 1 440 C Normal 1 600 C Normal 1 600 C Plus 1 760 C Plus 1 760 B Minus 1 620 B Minus 1 620 B Normal 1 800 ...

Страница 14: ...n 800 CFM Output for DIP Switch Combinations 5 and 6 Cooling Heating Model Speed Tap Switch 5 Switch 6 Cooling HP CFM WGPH4543 A Off Off 1 800 B On Off 1 700 C Off On 1 400 F D On On 1 225 WGPH4549 A Off Off 1 800 B On Off 1 700 C Off On 1 400 D On On 1 225 F WGPH4560 A Off Off 2 000 F B On Off 1 800 C Off On 1 600 D On On 1 400 DIP Switch Settings for Single and 2 Stage Thermostats Model Switch 3...

Страница 15: ...ithin limits Charge the unit on low stage 1 Purge the gauge lines 2 Connect the service gauge manifold to the access fittings Run the system for at least 10 minutes to allow the pressure to stabilize 3 Temporarily install a thermometer on the liquid small line near the liquid line access fitting with adequate contact and insulate for best possible reading 4 Check subcooling and superheat The 2 sta...

Страница 16: ... The return air filter must always be clean and sufficient air volume must pass through the indoor coil to prevent excessive discharge pressure and high pressure cutout Outside Air Into Return Duct Do not introduce cold outside air into the return duct of a heat pump installation Do not allow air entering the indoor coil to drop below 65 F 18ºC Air below this temperature will cause low discharge p...

Страница 17: ...V 208 TR C BK 1 R COMP CM BR 4 1 PLF BK Y S BK R 5 6 2 3 C R R O C W2 W1 G a t o t s m r e h T T2 T1 BU NOTE 2 PR L1 BU GND C L2 PR BK 60 1 0 4 2 8 0 2 7 8 9 BU BR W R R BK BK R Y BU BU R R DFT RVC LPS L 3 1 2 DC DFT DFT Y C R W2 O W1 Y1 G COM 4 5 6 PLF LVDR R R O O W2 HPS C If Used N G RVC See NOTE 4 SA If Used See NOTE 3 R Y BK BK BK OR OR W HPS Y BU BU BU BU Y Y LPS YCON OT2OT1 OTC O W W2 E W1 ...

Страница 18: ...K R 5 6 2 3 C R R O C W2 W1 G Y1 a t o t s m r e h T T2 T1 BU NOTE 2 PR L1 BU GND C L2 PR BK 60 1 0 4 2 8 0 2 7 8 9 BU BR W R R BK BK R Y BU BU R R DFT RVC LPS L 3 1 2 DC DFT DFT Y C R W2 O W1 Y1 G COM 4 5 6 PLF LVDR R R O O W2 HPS C If Used N G RVC See NOTE 4 SA If Used See NOTE 3 R Y BK BK BK OR OR W HPS Y BU BU Y BU BU Y Y LPS SOL BU Y BU YCON S0L OT2OT1 OTC O W W2 E W1 R YCON C OMO W2 ED OU TD...

Страница 19: ...A S T1 R L1 C NOTE 4 H F RCCF CM T2 C L2 Box H RCCF F C Y BR PR 2 24V 208 TR C BK 1 PR COMP CM BR BR PR 4 1 PLF PR BK Y S BK R BK 5 6 2 3 C R LVJB R BU BR W G Y R C W2 W1 G Y a t o t s m r e h T T2 T1 R BU NOTE 3 PR BU L1 GND C L2 PR BK 60 1 0 4 2 8 0 2 7 8 9 BU BR R R BK BK R C L G N 1 2 3 BU BU R G G G R EM G See NOTE 2 1 L 3 1 2 R W2 W1 Y G C 4 5 6 PLF EM 1 C See NOTE 2 If Used Thermostat N G 2...

Страница 20: ...time phone number in your correspondence Accessories To order accessories contact your Whirlpool Home Cooling and Heating dealer WPIO 362 2010 All rights reserved Registered Trademark TM Trademark of Whirlpool U S A Manufactured under license by Tradewinds Distributing Company LLC Jacksonville Florida Warranty provided by manufacturer All other trademarks are owned by their respective companies 2 ...

Отзывы: