WHL-038 Rev. 1.29.16
57
HARD FAULT COND F41
This error indicates there is an internal fault
in the circuit within the control connected to
the condensate switch.
1. Inspect the ground wires for damage or loose
connections.
2. Inspect the condensate wiring for damage and repair
as necessary.
3. Ensure no high voltage wires are routed in parallel with
the condensate low voltage wiring.
4. Replace control.
HARD FAULT LWCO F42
This error indicates there is an internal fault
in the LWCO circuit.
1. Inspect the ground wires for damage or loose
connections.
2. Inspect the LWCO wiring for damage and repair as
necessary.
3. Ensure no high voltage wires are routed in parallel with
the LWCO low voltage wiring.
4. Replace control.
CONTROL PROGRAMED PP
The control has been programmed by a
technician or the factory. After programming,
the control is left in a locked out mode.
Press
RESET
for at least 1 second to use the control.
OUTDOOR SENSOR FOU
PUMP ON 1:45P
There is an issue with the outdoor sensor. It
is shorted, damaged, or disconnected from
the boiler.
1. Check outdoor sensor connections and wiring. Ensure
the sensor and wiring are intact and that the sensor is
connected to the boiler.
2. Check the outdoor sensor resistance with an ohmmeter.
See table in this manual for correct outdoor sensor
resistance.
3. Replace the outdoor sensor.
The following blocking codes will block operation until the control determines the situation safe for boiler operation.
LOW WATER FLOW FL
PUMP OFF 4:32P
This indicates the flow switch is not activated.
1. Ensure boiler contains water and all valves are open.
2. Check the boiler circulator and ensure it is in good
operating condition (operating, wiring intact, etc.).
3. Inspect the wiring to the flow switch for damage and
repair as necessary.
4. Disconnect one wire from the flow switch and test for
continuity across the switch while flow is confirmed to be
present.
5. Remove flow switch and inspect switch paddle for
proper operation.
FLUE TEMP HIGH E07
PUMP ON TIME
This display indicates that the flue sensor
temperature is above 210
o
F. When this code
is displayed, the boiler will not respond to a
demand for heat. When the flue temperature
decreases below 194
o
F, the display will return
to normal and allow the boiler to respond to
a heat demand. The bottom line indicates the
status of the pump. The pump will remain on
when this error is displayed.
Check the flue for obstructions or any sign of damage,
especially signs of excessive heat. Repair as necessary.
Run the boiler and check the flue temperature with an
external thermometer. If the flue temperature on the
thermometer does not agree with the flue temperature
displayed in the status menu, inspect the wiring to
the flue temperature sensor in the boiler and repair as
necessary. If the wiring is intact, replace the flue sensor. If
the flue temperature is excessive on the status menu and
the test thermometer reads the same, check and adjust
combustion controls on the boiler.
TEMPER BLOCKING TT
PUMP ON
TT indicates there is a demand for heat on
the boiler, the pump is powered on, and the
supply sensor temperature is too high for
the boiler to ignite. This occurs because the
water temperature measured by the supply
sensor is higher than the tank temperature –
ignition diff setting.
This message will stay present until the water temperature
measured by the supply sensor is less than the tank
temperature – ignition diff setting.
TEMPER BLOCKING
PUMP ON
This screen indicates a demand for heat from
the DHW circuit. The pump is powered on and
the supply sensor temperature is too high for
the boiler to ignite. This occurs because the
water temperature measured by the supply
sensor is higher than the tank temperature –
ignition diff setting.
NOTE:
If there is a CH demand while this
screen is displayed, the screen may read:
TEMPER BLOCKING PRIO
This message will stay present until the water
temperature measured by the supply sensor is less than
the BOILER SUPPLY – boiler supply differential (5
o
F) or
DHW SETPOINT is satisfied and no longer calls for heat.
Содержание WBCETNG1000
Страница 14: ...WHL 038 Rev 1 29 16 14 Figure 6 Specifications and Dimensions NOTE All Dimensions Are Approximate ...
Страница 35: ...WHL 038 Rev 1 29 16 35 Figure 24 CascadeTermination Plug Detail Figure 25 Cascade Master and FollowerWiring ...
Страница 36: ...WHL 038 Rev 1 29 16 36 Figure 26 Internal Connection Diagram ...
Страница 65: ...WHL 038 Rev 1 29 16 65 Figure 44 Exterior Replacement Parts ...
Страница 66: ...WHL 038 Rev 1 29 16 66 Table 27 Optional Jacket Replacement Parts Part 15 Installing the Optional Jacket ...
Страница 73: ...WHL 038 Rev 1 29 16 73 Maintenance Notes ...