
WHL-038 Rev. 1.29.16
34
P. Wiring of Cascade System Communication Bus
1. A Cascade Bus Termination Plug has been installed on the
customer connection board of this boiler. The purpose of this
plug is to stabilize communication between multiple boilers
and reduce electrical “noise”. See Figure 22 for Cascade Bus
Termination Plug installation detail.
NOTE:
It is important that the termination plug in multiple
boilers (cascaded units) be installed as depicted in Figure 22.
Leave the plug installed in the J3 port on the Master boiler.
Remove the plug on intermediate Follower boilers. Move the
plug to the J4 port on the final Follower boiler.
2. Use standard CAT3 or CAT5 computer network patch cables
to connect the communication bus between each of the boilers.
These cables are readily available at any office supply, computer,
electronic, department or discount home supply store in varying
lengths. If you possess the skills you can also construct custom
length cables.
3. It is recommended to use the shortest length cable that will
reach between the boilers and create a neat installation. Do
not run unprotected cables across the floor where they may
become wet or damaged. Avoid running communication cables
parallel and close to or against high voltage (120 volt or greater)
wiring. Westinghouse recommends that the maximum length of
communication bus cables not exceed 200 feet.
4. Route the communication cables through one of the
knockouts in the cabinet.
5. Connect the boilers in a daisy chain configuration as shown
below. It is best to wire the boilers using the shortest wire
runs rather than trying to wire them in the order that they are
addressed. The communication bus jacks on the customer
connection panel are interchangeable so you can use either one
or both in any order to connect the cable.
If you have connected the boilers to each other properly, there
will be no open communication connection ports.
Q. Cascade Master Pump and Sensor Wiring
NOTE:
Place the Cascade Master label (included in shipping
envelope) on top of the boiler designated Master.
1. Connect the system pump hot wire to the terminal marked 7
(SYS PUMP).
2. Connect the system pump neutral to the 8 (SYS NEUT)
terminal and the pump ground wire to the 9 (SYS GND) terminal.
R. Cascade Follower Pump and Sensor Wiring
1. If it is desired to have the boiler control the boiler pump,
connect the boiler pump to the 1 (BOILER HOT), 2 (BOILER
NEUT), and 3 (BOILER GND) terminals.
2. If you are using an indirect fired water tank connected
directly to the follower boiler, connect the pump for it to the
4 (DHW HOT), 5 (DHW NEUT), and 6 (DHW GND) terminals.
If desired, an alarm bell or light can be connected to the alarm
contacts of the boiler. The normally closed alarm contact may
be used to turn a device off if the boiler goes into lockout
mode. The alarm contacts are rated 5 amps at 120 VAC.
To connect an alarm device, connect the power for the device
to the J10-2 (ALARM COM) terminal. Connect the alarm
device hot wire to the J10-1 (ALARM NO) terminal. Connect
the neutral or return of the alarm device to the neutral or
return of the power for the alarm device.
To connect a device that should be powered off during a boiler
lockout condition, follow the same instructions as above and
use the J10-3 (ALARM NC) terminal rather than the ALARM
NO terminal.
NOTE:
In a cascade system, the alarm output of the boiler
addressed as #1 will also be active if the master boiler has a
lockout condition. The alarm output of boilers addressed #2-
15 will only sound if a lockout condition occurs on that specific
boiler.
3. Connect the boiler pump to the terminals marked 1 (BOILER
HOT), 2 (BOILER NEUT), and 3 (BOILER GND).
4. Connect the system pipe sensor to the terminals marked 18
and 19 (SYS SENSOR).
5. Connect the outdoor sensor (if used) to the terminals
marked 12 and 13 (OUTDOOR SEN).
6. Connect the signal to start the system to the terminals
marked 14 and 15 (THERMOSTAT).
NOTE:
This signal can come from a room thermostat or a dry
contact closure. No power of any voltage should be fed into
either of these terminals.
N. Optional High Limit Manual Reset
NOTE:
Follow the more detailed instructions included with the
high limit manual reset kit for proper installation steps.
1. Thread the control well into the fitting provided on the
manifold using teflon thread tape.
2. Insert the control probe into the control well.
3. Secure the high limit manual reset box to the control well.
4. Locate and disconnect the red high limit manual reset wires.
Connect the two red wires to the manual reset box.
5. When installation is complete, power up the boiler and test
the reset according to the provided instructions. If the reset
operates properly, set the high limit temperature as described
in the provided instructions. When done, create a demand and
observe boiler function to verify the installation is working
properly.
To test, press the
RESET
and
v
buttons together for 3 - 5 seconds.
The LWCO will trip and indicate an F21 or F22 fault code on the
display. To clear the error, press
RESET
.
Содержание WBCETNG1000
Страница 14: ...WHL 038 Rev 1 29 16 14 Figure 6 Specifications and Dimensions NOTE All Dimensions Are Approximate ...
Страница 35: ...WHL 038 Rev 1 29 16 35 Figure 24 CascadeTermination Plug Detail Figure 25 Cascade Master and FollowerWiring ...
Страница 36: ...WHL 038 Rev 1 29 16 36 Figure 26 Internal Connection Diagram ...
Страница 65: ...WHL 038 Rev 1 29 16 65 Figure 44 Exterior Replacement Parts ...
Страница 66: ...WHL 038 Rev 1 29 16 66 Table 27 Optional Jacket Replacement Parts Part 15 Installing the Optional Jacket ...
Страница 73: ...WHL 038 Rev 1 29 16 73 Maintenance Notes ...