
WHL-038 Rev. 1.29.16
12
2. Indoor Combustion Air in Confined or Unconfined Space
This boiler requires fresh, uncontaminated air for safe operation
and must be installed in a mechanical room where there is
adequate combustion and ventilating air.
NOTE: To prevent
combustion air contamination, see Table 1.
Combustion air from the indoor space can be used if the space
has adequate area or when air is provided through a duct or
louver to supply sufficient combustion air based on the boiler
input. Never obstruct the supply of combustion air to the boiler.
If the boiler is installed in areas where indoor air is contaminated
(see Table 1) it is imperative that the boiler be installed as
direct vent so that all combustion air is taken directly from the
outdoors into the boiler intake connection.
Unconfined space
is space with volume greater than 50 cubic
feet per 1,000 BTU/hr (4.8 cubic meters per kW) of the total
input rating of all fuel-burning appliances installed in that space.
Rooms connected directly to this space through openings not
furnished with doors are considered part of the space. See
Venting Section for details.
Confined space
is space with volume less than 50 cubic feet per
1,000 BTU/hr (4.8 cubic meters per kW) of the total input rating
of all fuel-burning appliances installed in that space. Rooms
connected directly to this space through openings not furnished
with doors are considered part of the space.
When drawing combustion air from inside a conventionally
constructed building to a confined space, such space should be
provided with two permanent openings: one located 6” (15 cm)
below the space ceiling, the other 6” (15cm) above the space
floor. Each opening should have a free area of one square inch
per 1,000 BTU/hr (22cm
2
/kW) of the total input of all appliances
in the space, but not less than 100 square inches (645cm
2
).
If the confined space is within a building of tight construction, air
for combustion must be obtained from the outdoors as outlined
in the Venting section of this manual.
When drawing combustion air from the outside into the
mechanical room, care must be taken to provide adequate
freeze protection.
Failure to provide an adequate supply of fresh combustion air can
cause poisonous flue gases to enter the living space, resulting
in severe personal injury or death. To prevent combustion air
contamination, see Table 1.
G. Prevent Combustion Air Contamination
Install intake air piping for the boiler as described in the Venting
Section, this manual. Do not terminate exhaust in locations that
can allow contamination of intake air.
Ensure that the intake air will not contain any of the contaminants
in Table 1. Contaminated air will damage the boiler, resulting in
possible substantial property damage, severe personal injury, or
death. For example, do not pipe intake air near a swimming pool
or laundry facilities. These areas always contain contaminants.
Products to Avoid
Areas Likely to Have
Contaminants
Spray
cans
containing
fluorocarbons
Dry cleaning / laundry areas
and establishments
Permanent wave solutions
Swimming pools
Chlorinated waxes / cleaners
Metal fabrication plants
Chlorine-based swimming pool
chemicals
Beauty shops
Calcium chloride used for thawing Refrigeration repair shops
Sodium chloride used for water
softening
Photo processing plants
Refrigerant leaks
Auto body shops
Paint or varnish removers
Plastic manufacturing plants
Hydrochloric or Muriatic acid
Furniture refinishing areas
and establishments
Cements and glues
New building construction
Antistatic fabric softeners used in
clothes dryers
Remodeling areas
Chlorine-type bleaches, laundry
detergents, and cleaning solvents
Garages and workshops
Adhesives used to fasten building
products
Table 1 - Products and Areas Likely to Have Contaminants
NOTE: DAMAGE TO THE BOILER CAUSED BY EXPOSURE
TO CORROSIVE VAPORS IS NOT COVERED BY
WARRANTY.
(Refer to the limited warranty for complete
terms and conditions.)
H. Removing a Boiler from a Common Vent System
Failure to follow all instructions can result in flue gas spillage
and carbon monoxide emissions, causing severe personal
injury or death.
Do not install the boiler into a common vent with any other
appliance. This will cause flue gas spillage or appliance
malfunction, resulting in possible substantial property
damage, severe personal injury, or death.
When removing an existing boiler, follow the steps below.
1. Seal any unused openings in the common venting system.
2. Visually inspect the venting system for proper size and
horizontal pitch to determine if there is blockage, leakage,
corrosion, or other deficiencies that could cause an unsafe
condition.
3. If practical, close all building doors, windows, and doors
between the space in which the boiler remains connected to
the common venting system and other spaces in the building.
Turn on clothes dryers and any appliances not connected to
the common venting system. Turn on any exhaust fans, such
as range hoods and bathroom exhausts, at maximum speed.
Do not operate a summer exhaust fan. Close all fireplace
dampers.
4. Place in operation the appliance being inspected. Follow the
lighting instructions. Adjust the thermostat so the appliance
will operate continuously.
5. Test for spillage at the draft hood relief opening after 5
Содержание WBCETNG1000
Страница 14: ...WHL 038 Rev 1 29 16 14 Figure 6 Specifications and Dimensions NOTE All Dimensions Are Approximate ...
Страница 35: ...WHL 038 Rev 1 29 16 35 Figure 24 CascadeTermination Plug Detail Figure 25 Cascade Master and FollowerWiring ...
Страница 36: ...WHL 038 Rev 1 29 16 36 Figure 26 Internal Connection Diagram ...
Страница 65: ...WHL 038 Rev 1 29 16 65 Figure 44 Exterior Replacement Parts ...
Страница 66: ...WHL 038 Rev 1 29 16 66 Table 27 Optional Jacket Replacement Parts Part 15 Installing the Optional Jacket ...
Страница 73: ...WHL 038 Rev 1 29 16 73 Maintenance Notes ...