WHL-038 Rev. 1.29.16
45
Screen
Description
Function 1
Factory Program Mode
MODE
INDIRECT 1
This indicates that the control is
configured correctly. Do not change
this setting.
Function 3
DHW Tank Max Temp
DHW TANK MAX TEMP
180
o
F 3
This is the maximum temperature
that can be selected in boiler settings
for the DHW tank. Factory Default is
180
o
F. (Range: 95
o
F to 180
o
F)
Function 6
DHW Post Pump Time
DHW POST PUMP TIME
0 MINUTES 6
The indirect pump has the ability to
post purge energy from the boiler
to run the pump after the set point
has been achieved. Please note that
running the pump for a time greater
than 5 minutes may cause tank
energy to be released back to the
heat exchanger. Factory Default of 0
Minutes. (Range: 0 – 10 minutes)
Function 7
Warm Weather Shutoff
WARM WEATHER OFF
68
o
F 7
When used with an outdoor sensor,
warm weather shut down will
disable the boiler if the programmed
outdoor temperature is exceeded.
Default: 68
o
F (Range: 41
o
F to 122
o
F).
Function 8
Min Outdoor Temp
MIN OUTDOOR TEMP
5
o
F 8
Sets the minimum outdoor design
temperature for the system. Default:
5
o
F (Range: -49
o
F to 32
o
F).
Function 9
Max Supply Temp
MAX SUPPLY TEMP
180
o
F 9
Sets the maximum design supply
temperature based on the minimum
outdoor
design
temperature.
Default: 180
o
F (Range: 77
o
F to
190
o
F).
Function 10
Max Outdoor Temp
MAX OUTDOOR TEMP
68
o
F 10
Sets the maximum outdoor design
temperature for the system design.
Default: 68
o
F (Range 32
o
F to 190
o
F).
Function 11
Min Supply Temp
MIN SUPPLY TEMP
95
o
F 11
Sets the design supply water
temperature based on the maximum
outdoor
design
temperature.
Default: 95
o
F (Range: 32
o
F to 190
o
F).
Function 12
Min Boiler Temp
MIN BOILER TEMP
68
o
F 12
Sets the design minimum heat
curve temperature for central heat.
Default: 68
o
F (Range: 32
o
F to 190
o
F).
Function 13
CH Post Pump Time
CH POST PUMP TIME
0 MINUTES 13
Allows the user to set the boiler
pump post purge time once the
thermostat is satisfied. Default: 0
minutes (Range: 0 – 10 minutes).
Screen
Description
Function 14
DHW Priority
DHW PRIORITY
30 MINUTES 14
Allows the user to set the maximum
run time for the indirect fired water
heater and the minimum run time
for central heating. Default: 30
minutes (Range: 0 – 60 minutes).
Function 15
Cascade Address
CASCADE ADDRESS
0 15
Bus addressing boilers (maximum
boilers allowed is eight (8) in a
cascade system). Master Boiler
address is 0 and Following Boilers
are addressed 1 thru 15. Default: 0
(Range: 0 – 15). NOTE: ONLY USE
ADDRESS 8.
Function 16
Optional Inputs
OPTIONAL INPUT
OFF 16
Allows the user to select optional
inputs to control or monitor the
system. Default: OFF (Range: Off /
Booster Board / 0-10 Volt).
Function 17
0-10 Volt Function
0-10 VOLT FUNCTION
TEMPERATURE 17
Controls boiler modulation through
temperature
control.
Factory
Default = Temperature (Range:
Temperature or Fan Speed).
Function 18
Step Modulation Mode
STEP MODULATE MODE
ON 18
Allows the user to turn ON step
modulation, which regulates burner
output in six steps at one minute
intervals. Step modulation will start
at the last modulation rate of the
boiler and work up one minute at a
time. Default: ON (Selection: OFF or
ON).
Function 19
Boiler DHW Temp
BOILER SUPPLY DHW
180
o
F 19
Allows the user to program the
boiler supply water temperature to
the indirect heat exchanger during
a demand cycle. Default: 180
o
F
(Range: 119
o
F to 190
o
F).
Function 20
Water Safety Input
WATER SAFETY INPUT
NONE 20
The user can select various water
safety inputs used in the boiler
system. Default: NONE (Range:
NONE / Flow Switch / Water
Pressure).
Function 21
Error Outdoor Sensor
ERROR OUTD SENSOR
OFF 21
Allows the user to set the control
to display an error message if an
outdoor sensor is open or shorted.
NOTE: This error does not stop the
boiler from running. Factory Default:
OFF (Range: ON / OFF / PHOEN ON).
Function 22
Adjust Boiler Output %
ADJ BOILER OUTPUT
100% 22
Adjusts the boiler output down
from 100% to 50%. Factory Default:
100%. (Range: 100% – 50%)
Содержание WBCETNG1000
Страница 14: ...WHL 038 Rev 1 29 16 14 Figure 6 Specifications and Dimensions NOTE All Dimensions Are Approximate ...
Страница 35: ...WHL 038 Rev 1 29 16 35 Figure 24 CascadeTermination Plug Detail Figure 25 Cascade Master and FollowerWiring ...
Страница 36: ...WHL 038 Rev 1 29 16 36 Figure 26 Internal Connection Diagram ...
Страница 65: ...WHL 038 Rev 1 29 16 65 Figure 44 Exterior Replacement Parts ...
Страница 66: ...WHL 038 Rev 1 29 16 66 Table 27 Optional Jacket Replacement Parts Part 15 Installing the Optional Jacket ...
Страница 73: ...WHL 038 Rev 1 29 16 73 Maintenance Notes ...