Troubleshooting and Maintenance
6-8
6
Do not perform any withstand voltage test!
If needed, consult WEG.
The inverters require low maintenance when properly installed and operated . Table 6.3 presents main procedures
and time intervals for preventive maintenance. Table 6.4 provides recommended periodic inspections to be
performed every 6 months after inverter start-up.
Table 6.3
- Preventive maintenance
Maintenance
Interval
Instructions
Fan replacement
After 50.000 operating hours.
(1)
Replacement procedure shown in figures 6.1 and 6.2.
Keypad battery replacement
Every 10 years.
Refer to chapter 4.
Electrolytic
capacitors
If the inverter is stocked (not
being used):
“Reforming”
Every year from the manufacturing
date printed in the inverter
identification label (refer to item
2.4).
Apply power to the inverter (voltage between 200 and
230 Vac, single-phase or three-phase, 50 or 60 Hz) for at
least one hour. Then, disconnect the power supply and wait
at least 24 hours before using the inverter (reapply power).
Inverter is being used:
replace
Every 10 years.
Contact WEG technical support to obtain replacement
procedures.
Note:
(1)
The inverters are factory set for automatic fan control (P0352=2), which means that they will be turned on
only when the heatsink temperature exceeds a reference value. Therefore, the operating hours of the fan will
depend on the inverter usage conditions (motor current, output frequency, cooling air temperature, etc.).
The inverter stores the number of operating hours of the fan in parameter P0045. When this parameter
reaches 50.000 operating hours, the keypad display will show alarm A177.
Component
Problem
Corrective Action
Terminals, connectors
Loose screws
Tighten
Loose
connectors
Fans / Cooling system
Dirty fans
Cleaning
Abnormal acoustic noise
Replace fan. Refer to figure 6.1.
Blocked fan
Check the fan connection.
Abnormal
vibration
Dust in the cabinet air filter
Cleaning or replacement.
Printed circuit boards
Accumulation of dust, oil, humidity, etc.
Cleaning
Odor
Replacement
Power module /
Accumulation of dust, oil, humidity, etc.
Cleaning
Power connections
Loose connection screws
Tighten
DC bus capacitors
Discoloration / odor / electrolyte leakage
Replacement
Expanded or broken safety valve
Frame
expansion
Power resistors
Discoloration
Replacement
Odor
Heatsink
Dust accumulation
Cleaning
Dirty
Table 6.4
5HFRPPHQGHGSHULRGLFLQVSHFWLRQV(YHU\PRQWKV
Содержание 105 A
Страница 3: ...2 Revision Description Chapter 1 First Edition 2 General Revision Summary of Revisions...
Страница 17: ...General Instructions 2 10 2...
Страница 49: ...Installation and Connection 3 32 3...
Страница 63: ...First Time Power Up and Start Up 5 10 5...
Страница 79: ...Option Kits and Accessories 7 6 7...
Страница 88: ...Technical Specifications 8 9 8 Frame B Figure 8 3 Inverter dimensions frame B Dimensions in mm in...
Страница 89: ...Technical Specifications 8 10 8 Frame C Figure 8 4 Inverter dimensions frame C Dimensions in mm in...
Страница 90: ...Technical Specifications 8 11 8 Frame D Figure 8 5 Inverter dimensions frame D Dimensions in mm in...