Installation and Connection
3-20
3
Figure 3.16 a)
6LJQDOVDWFRQQHFWRU;&'LJLWDOLQSXWVZRUNLQJDV$FWLYH+LJK
Connector XC1
Factory Default Function
Specifications
1
+REF
Positive reference for
potentiometer
Output v5.4 V, ±5 %.
Maximum output current: 2 mA
2
AI1+
Analog input #1:
Speed reference (remote)
Differential
Resolution: 12 bits
Signal: 0 to 10 V (R
IN
NWRP$WRP$5
IN
Maximum voltage: ±30 V
3
AI1-
4
REF-
Negative reference for
potentiometer
Output voltage: -4.7 V, ±5 %.
Maximum output current: 2 mA
5
AI2+
Analog input #2:
No function
Differential
Resolution: 11 bits + signal
Signal: 0 to ±10 V (R
IN
NWRP$WRP$5
IN
Maximum voltage: ±30 V
6
AI2-
7
AO1
Analog output #1:
Speed
Galvanic Isolation
Resolution: 11 bits
Signal: 0 to 10 V (R
L
NWRP$WRP$5
L
Protected against short-circuit.
8
AGND
(24 V)
Reference (0 V) for the analog
outputs
&RQQHFWHGWRWKHJURXQGIUDPHWKURXJKLPSHGDQFHUHVLVWRULQ
parallel with a 22 nF capacitor.
9
AO2
Analog output #2:
Motor current
Galvanic Isolation
Resolution: 11 bits
Signal: 0 to 10 V (R
L
NWRP$WRP$5
L
Protected against short-circuit.
10
AGND
(24 V)
Reference (0 V) for the analog
outputs
&RQQHFWHGWRWKHJURXQGIUDPHWKURXJKLPSHGDQFHUHVLVWRULQ
parallel with a 22 nF capacitor.
11
DGND*
Reference (0 V) for the 24 Vdc
power supply
&RQQHFWHGWRWKHJURXQGIUDPHWKURXJKLPSHGDQFHUHVLVWRULQ
parallel with a 22 nF capacitor.
12
COM
Common point of the digital
inputs
13
24 Vdc
24 Vdc power supply
24 Vdc power supply, ±8 %.
Capacity: 500 mA.
Note:
In the models with the 24 Vdc external control power supply
(CFW11XXXXXXOW) the terminal 13 of XC1 becomes an input, i.e., the
user must connect a 24 V power supply for the inverter (refer to the section
7.1.3 for more details). In all the other models this terminal is an output,
i.e., the user has a 24 V power supply available there.
14
COM
Common point of the digital
inputs
15
DI1
Digital input #1:
Start / Stop
6 isolated digital inputs
+LJKOHYHO9
/RZOHYHO9
Maximum input voltage = 30 V
Input current: 11mA @ 24 Vdc
16
DI2
Digital input #2:
Direction of rotation (remote)
17
DI3
Digital input #3:
No function
18
DI4
Digital input #4:
No function
19
DI5
Digital input #5:
Jog (remote)
20
DI6
Digital input #6:
2
nf
ramp
21
NC1
Digital output #1 DO1 (RL1):
No fault
Contact rating:
Maximum voltage: 240 Vac
Maximum current: 1 A
NC - Normally closed contact;
C - Common;
NO - Normally open contact.
22
C1
23
NO1
24
NC2
Digital output #2 DO2 (RL2):
N > N
X
- Speed > P0288
25
C2
26
NO2
27
NC3
Digital output #3 DO3 (RL3):
N* > N
X
- Speed reference >
P0288
28
C3
29
NO3
CCW
CW
N
rpm
amp
3.2.5 Control Connections
The control connections (analog inputs/outputs, digital inputs/outputs), shall be performed in connector XC1
of the CC11 control board.
Functions and typical connections are presented in figures 3.16
a)
and
b)
.
Содержание 105 A
Страница 3: ...2 Revision Description Chapter 1 First Edition 2 General Revision Summary of Revisions...
Страница 17: ...General Instructions 2 10 2...
Страница 49: ...Installation and Connection 3 32 3...
Страница 63: ...First Time Power Up and Start Up 5 10 5...
Страница 79: ...Option Kits and Accessories 7 6 7...
Страница 88: ...Technical Specifications 8 9 8 Frame B Figure 8 3 Inverter dimensions frame B Dimensions in mm in...
Страница 89: ...Technical Specifications 8 10 8 Frame C Figure 8 4 Inverter dimensions frame C Dimensions in mm in...
Страница 90: ...Technical Specifications 8 11 8 Frame D Figure 8 5 Inverter dimensions frame D Dimensions in mm in...