First Time Power-Up and Start-Up
5-4
5
)LJXUHFRQW
- Oriented Start-up
Step
Action/Result
Display indication
10
- If needed, change the
value of P0296 according
to the line rated voltage.
To do so, press
"Select"
.
This modification will
affect P0151, P0153,
P0185, P0321, P0322,
P0323, and P0400.
Config
LOC
0rpm
Reset
13:48 Select
Type of Control
P0202: V/F 60 HZ
Line Rated Voltage
P0296: 440 - 460 V
11
- If needed, change the
value of P0298 according
to the inverter application.
To do so, press
"Select"
.
This modification will
affect P0156, P0157,
P0158, P0401, P0404
and P0410 (this last one
only if P0202 = 0, 1, or
2 – V/f control). The time
and the activation level of
the overload protection
will be affected as well.
Config
LOC
0rpm
Reset
13:48 Select
Line Rated Voltage
P0296: 440 - 460 V
Application
P0298: Heavy Duty
12
- If needed, change the
value of P0398 according
to the motor service factor.
To do so, press
“Select”
.
This modification will
affect the current value
and the activation time
of the motor overload
function.
Config
LOC
0rpm
Reset
13:48 Select
Application
P0298: Heavy Duty
Motor Service Factor
P0398: 1.15
13
- If needed, change
the value of P0400
according to the motor
rated voltage. To do
so, press
“Select”
. This
modification adjusts the
output voltage by a factor
x = P0400/P0296.
Config
LOC
0rpm
Reset
13:48 Select
Motor Service Factor
P0398: 1.15
Motor Rated Voltage
P0400: 440 V
14
- If needed, change the
value of P0401 according
to the motor rated current.
To do so, press
“Select”
.
This modification will
affect P0156, P0157,
P0158, and P0410.
Config
LOC
0rpm
Reset
13:48 Select
Motor Rated Voltage
P0400: 440V
Motor Rated Current
P0401: 13.5 A
Step
Action/Result
Display indication
15
- If needed, set P0402
according to the motor
rated speed. To do so,
press
“Select”
. This
modification affects
P0122 to P0131, P0133,
P0134, P0135, P0182,
P0208, P0288, and
P0289.
Config
LOC
0rpm
Reset
13:48 Select
Motor Rated Current
P0401: 13.5 A
Motor Rated Speed
P0402: 1750 rpm
16
- If needed, set P0403
according to the motor
rated frequency. To do
so, press
“Select”
. This
modification affects
P0402.
Config
LOC
0rpm
Reset
13:48 Select
Motor Rated Speed
P0402: 1750 rpm
Motor Rated Frequency
P0403: 60 Hz
17
- If needed, change the
value of P0404 according
to the motor rated power.
To do so, press
“Select”
.
This modification affects
P0410.
Config
LOC
0rpm
Reset
13:48 Select
Motor Rated Frequency
P0403: 60 Hz
Motor Rated Power
P0404: 4hp 3kW
18
- This parameter will only
be visible if the encoder
board ENC1 is installed in
the inverter.
- If there is an encoder
connected to the motor,
set P0405 according
to the encoder pulses
number. To do so, press
“Select”
.
Config
LOC
0rpm
Reset
13:48 Select
Motor Rated Power
P0404: 4hp 3kW
Encoder Pulses Number
P0405: 1024 ppr
19
- If needed, set P0406
according to the motor
ventilation. To do so, press
“Select”
.
- To complete the
Oriented Start-Up routine,
press
“Reset”
(left soft key) or
.
Config
LOC
0rpm
Reset
13:48 Select
Encoder Pulses Number
P0405: 1024 ppr
Motor Ventilation
P0406: Self-Vent.
20
- After few seconds, the
display returns to the
Monitoring Mode.
Ready
LOC
0rpm
13:48
Menu
0
rpm
0.0
A
0.0
Hz
Содержание 105 A
Страница 3: ...2 Revision Description Chapter 1 First Edition 2 General Revision Summary of Revisions...
Страница 17: ...General Instructions 2 10 2...
Страница 49: ...Installation and Connection 3 32 3...
Страница 63: ...First Time Power Up and Start Up 5 10 5...
Страница 79: ...Option Kits and Accessories 7 6 7...
Страница 88: ...Technical Specifications 8 9 8 Frame B Figure 8 3 Inverter dimensions frame B Dimensions in mm in...
Страница 89: ...Technical Specifications 8 10 8 Frame C Figure 8 4 Inverter dimensions frame C Dimensions in mm in...
Страница 90: ...Technical Specifications 8 11 8 Frame D Figure 8 5 Inverter dimensions frame D Dimensions in mm in...