Receiver Wiring
Pin 1
Signal output
Muting indicator muting terminal
Pin 2
24 V DC
Supply Voltage 24 V DC
Pin 3
OSSD 1 output
PLC or relay
Pin 4
Acknowledge
free
Pin 5
Contactor monitor
free
Pin 6
OSSD 2 output
PLC or relay
Pin 7
Ground
(0 V)
Supply Voltage 0 V
Pin 8
Earth/shield
Operational earth
Changes in the calculation of safety clearance must be taken into consideration in the “reduced resolution”
operating mode.
5.4.4.2 Reduced Resolution Procedure
Start
Repeatedly move the
object through the
safety field
The number of blanked beams
appears at the display,
and the blanking LED blinks
Press the enter button
on the receiver
Does 00
appear at the display
and does the failure
LED blink?
The light curtain
boots and enables
the outputs
The light curtain
is ready for operation
Display at Receiver
Serial Communication
Cascading
Timing
Restart Inhibit
8
7
6
5
4
3
2
1
ON OFF
Contactor Monitoring
Reduced Resolution
Fix Blanking
S1
Reduced Resolution
Operating Mode
DIP Switch Settings: Receiver
Set the
reduced resolution
DIP switch
no
1. Remove the object from the safety field
2. Reset the reduced resolution DIP switch
3. Switch the light curtain on and off
Starting with the pilot
beam, move the test
rod through the safety
field
Does the total
number of all beams
appear at the
display?
no
The following must be observed:
The safety field’s pilot beam may not be continuously interrupted.