16
EN
Receiver Wiring
Pin 1
Signal output
free
Pin 2
24 V DC
Supply Voltage 24 V DC
Pin 3
OSSD1 output
PLC or relay
Pin 4
Acknowledge
free
Pin 5
Contactor monitor
free
Pin 6
OSSD 2 output
PLC or relay
Pin 7
Ground
(0 V)
Supply Voltage 0 V
Pin 8
Earth/shield
Operational earth
DIP Switch Settings: Receiver
Serial Communication
Cascading
Timing
Restart Inhibit
8
7
6
5
4
3
2
1
ON OFF
Contactor Monitoring
Reduced Resolution
Fix Blanking
S1
4.2 Default Settings
The Light Curtain offers various types of functions without any additional devices. The following table provides an
overview of possible functions, as well as the product’s respective default settings.
Function Type
Default Settings
Safety Operating Mode
Active
Start-Up inhibit and Restart Inhibit
Not active
Contactor Monitoring
Not active