Receiver Wiring
Pin 1
Signal output
Unused
Pin 2
24 V DC
Supply Voltage 24 V DC
Pin 3
OSSD 1 output
PLC or relay
Pin 4
Acknowledge
free
Pin 5
Contactor monitor
free
Pin 6
OSSD 2 output
PLC or relay
Pin 7
Ground (0 V)
Supply Voltage 0 V
Pin 8
Earth/shield
Operational earth
Up to 25 % of the beams, but no more than 20 beams in all, can be blanked in the fix blanking operating
mode.
5.4.1.2 Fix Blanking Procedure
Start
Set the fix blanking
DIP switch
The number of blanked beams
appears at the display, and the
blanking LED blinks
Press the enter button
on the receiver
Does 00 appear
at the display and does
the failure LED
blink?
The light curtain
boots and enables
the outputs
The light curtain is
ready for operation
Display at Receiver
Serial Communication
Cascading
Timing
Restart Inhibit
8
7
6
5
4
3
2
1
ON OFF
Contactor Monitoring
Reduced Resolution
Fix Blanking
S1
Fix Blanking Operating Mode
DIP Switch Settings: Receiver
Position the object
to be suppressed
within the safety field
no
For example,
2 beams are blanked
1. Remove the object from the safety
field
2. Reset the fix blanking DIP switch
3. Switch the light curtain on and off
Display at Receiver
Start with the pilot
beam, move the test
rod through the safety
field
Does the total
number of all beams
appear at the
display?
no
The following must be observed:
The safety field’s pilot beam may not be continuously interrupted.