33
Prerequisites for use:
• Only those objects which actually protrude into or pass through the safety field during operation may be
used for the configuration.
• Testing must be performed in order to determine whether or not floating blanking can be used, whereby
all possible object arrangements (practical experience) have to be tested.
• The “restart inhibit” and “contactor monitoring” functions can be activated as required in the auto-floating
blanking operating mode.
• A warning lamp must be additionally connected.
• Safety clearance is influenced by auto-floating blanking.
• The operation mode „Auto Floating Blanking“ can only be parameterized via the serial interface. (view
operating instruction B-wsafe)
5.4.3.2 Auto Floating Blanking Procedure
The configuration of the operating mode is made like in case of Floating Blanking (section 5.4.2.2)
Schematic Diagram, Auto-Floating Blanking
8) Serial Communication
7) Timing
6) Cascading
5) Reduced Resolution
3) Fix Blanking
2) Contactor Monitoring
1) Restart Inhibit
8) Serial Communication
7) Timing
6) Cascading
5) Reduced Resolution
3) Fix Blanking
2) Contactor Monitoring
1) Restart Inhibit
89
2
88
Receiver
Control Panel
Emitter
Control Panel
Socket
Socket
Plug
Plug
Failure (RD)
Normal
Operation (GN)
Enter Button
Enter Button
Failure (RD)
Display 2
Display 1
Blanking
Alignment (YE)
OSSD off (RD)
OSSD on (GN)
Dip Switch S1
2
1
3
4
4
2
6
1
3
5
7
8
24 V
SM0-00CA 000C1
Plug Receiver
Contactor Monitor
Acknowledge
OSSD 1
24 V
Safety PLC
(Cat. 4; PL e; SIL3)
or Safety Relay
24 V
OSSD 2
0 V
Signal Output
Earth/shield
Muting
Muting Indicator
24 V
GND
0 V
Plug Emitter
Earth/shield
Please observe the following:
The “restart inhibit” and “contactor monitoring” functions can be activated as required in the auto-floating
blanking operating mode.