21.
KETTLE VENTING INSTRUCTIONS
1.
Remove Access Panel from
back of main kettle console.
2.
Turn kettle ON and set temperature
control to
10
, heat the empty kettle
until unit cycles off.
3.
Vent kettle by pulling Valve Ring
eight to fifteen times, holding
valve open for two seconds
each time.
NOTE
: If unit cycles ON, stop
venting and wait for kettle to cycle
OFF before continuing.
4.
Turn kettle OFF. Add cold water
to kettle until its surface
temperature is below 100°F. The
pressure gauge needle should
be in the green zone, indicating
a vacuum in the kettle’s jacket.
5.
If needle is in the green zone then
venting was successful. If not
repeat procedure.
2
3
5
6
7
8
9
1
4
10
OFF
50
0
100
150
200
250
300
350
400
40
50
60
0
10
20
30
psi
kPa
V
EN
T
A
IR
50
0
100
150
200
250
300
350
400
40
50
60
0
10
20
30
psi
kPa
V
EN
T
A
IR
The following venting procedure should be followed when the
Vacuum/Pressure Gauge needle is in the "VENT AIR" zone:
NOTE
: Check for and eliminate leaks prior to venting
(see REPAIRING LEAKS IN STEAM JACKETED KETTLE
FITTINGS).
Pressure
Relief Valve
Access
Panel
Valve
Ring
RESERVOIR FILL PROCEDURES
The kettle's water level must be maintained at the proper
level. Under normal operating conditions, the sealed
water reservoir should never require the addition of water.
If the red "low water" light comes on during use (while the
kettle is in an upright position), the water level has reached
a critically low level. The low water protection control has
automatically shut off the gas burner. The following
procedure must be completed before further use:
NOTE:
Have a qualified service
technician repair the leakage
problem and add water to the
unit. Ensure that the red "low
water" light is on when the kettle
is upright. On tilting kettles, it is normal for the red light to
come on when the kettle is in a tilted position.
1.
Ensure kettle is at room temperature
and pressure gauge showing zero or
less pressure.
2.
Shut off power to the kettle at the
fused disconnect switch.
3.
Remove Console Cover and Access Panel.
4.
Pull Pressure Relief Valve Ring open
to insure vessel is not pressurized.
5.
Remove 1/4" copper tubing and
reducer bushing.
6.
Add distilled water using a funnel if
necessary. Fill the unit to the high
level mark on the Sight Glass.
7.
Apply a thread sealant (i.e. Teflon
tape) to the reducer bushing threads
and replace.
8.
Replace Console Cover and Access
Panel.
9.
Restore power to unit at the fused
disconnect switch.
10.
The kettle must now be vented.
(Refer to the KETTLE VENTING
INSTRUCTIONS).
Important
-
Pull ring on
Pressure
Relief Valve
prior to
removal to
insure vessel
is not
pressurized.
50
0
100
150
200
250
300
350
400
40
50
60
0
10
20
30
psi
kPa
V
EN
T
A
IR
Pressure
Relief Valve
Access
Panel
Drain Plug Location
Valve
Ring
Console
Cover
Improper refilling of kettle jacket
will result in irreversible damage
to unit.
WARNING:
!
Sight Glass