4.
GENERAL
Installation of the kettle must be accomplished by qualified
electrical installation personnel working to all applicable local
and national codes. Improper installation of product could
cause injury or damage.
This equipment is built to comply with applicable standards
for manufacturers. Included among those approval agencies
are: UL, NSF, ASME/Ntl. Bd., CSA, CGA, ETL, and others.
Many local codes exist, and it is the responsibility of the
owner/installer to comply with these codes.
RECEIVING INSPECTION
Before unpacking visually inspect the unit for evidence of
damage during shipping.
If damage is noticed, do not unpack the unit, follow Shipping
Damage Instructions shown below.
SHIPPING DAMAGE INSTRUCTIONS
If shipping damage to the unit is discovered or suspected,
observe the following guidelines in preparing a shipping
damage claim.
1. Write down a description of the damage or the reason for
suspecting damage as soon as it is discovered. This will
help in filling out the claim forms later.
2. As soon as damage is discovered or suspected, notify
the carrier that delivered the shipment.
3. Arrange for the carrier's representative to examine the
damage.
4. Fill out all carrier claims forms and have the examining
carrier sign and date each form.
INSTALLATION
UNCRATING
Caution
:
Straps under tension and will snap when cut.
Carton may contain staples and skid contains nails.
Use proper safety equipment and precautions.
Unit is heavy use adequate help or lifting equipment as
needed.
1.
Carefully cut any straps from container.
2.
Lift off carton.
3.
Inspect for hidden damage. If found refer to “SHIPPING
DAMAGE INSTRUCTIONS”.
4.
Cut strap holding unit.
5.
Remove manual from kettle pot. Write down the model #
and serial # of the unit onto the front of this manual.
6.
Lift kettle off skid and move kettle to its installation
location.
7.
Discard packaging material according to local and or
state requirements.
VENTILATION
Operation of these units can produce significant levels of
steam and condensate, it is recommended they be installed
under a ventilation hood in a room which has provisions for
adequate make up air. Further information can be obtained
by referring to the U.S.A. National Fire Protection
Associations NFPA96 regulations. These standards have also
been adopted by the National Building Code in Canada.
POSTITIONING
The first installation step is to refer to the Specification Sheets
or Specification Drawings for detailed clearance and drain
requirements in order to determine the location of the kettle.
Next, carefully cut open the shipping carton for easy removal
of the kettle
.
Position the kettle in it's permanent location, and level the
kettle by turning the adjustable flanged feet. Once positioned
and leveled, permanently secure the kettle's flanged feet to
the floor using 5/16" lag bolts and floor anchors (supplied by
the installer). There are three bolts required to secure each of
the flanged feet.
CLEARANCE REQUIREMENTS
Back - 0, Left Side - 0, Right Side - 12” (Minimum
recomended clearance for service)
Unit with
Model #
Unit
shipping
box
KEL-25
210 lbs.
245 lbs.
KEL-30
230 lbs.
265 lbs.
KEL-40
280 lbs.
315 lbs.
KEL-60
330 lbs.
365 lbs.
KEL-80
385 lbs.
420 lbs.
KEL-100
415 lbs.
450 lbs.
KEL-25-T
290 lbs.
325 lbs.
KEL-40-T
360 lbs.
395 lbs.
KEL-60-T
415 lbs.
450 lbs.
KEL-80-T
470 lbs.
505 lbs.
KEL-100-T
520 lbs.
555 lbs.
KEL-40-TSH
360 lbs.
395 lbs.
KEL-60-TSH
415 lbs.
450 lbs.
KEL-40-SH
280 lbs.
315 lbs.
KEL-60-TSH
340 lbs.
375 lbs.
APPROXIMATE WEIGHTS
Содержание Cleveland KEL-100
Страница 19: ...18 WIRING DIAGRAM 200 240v...
Страница 20: ...19 WIRING DIAGRAM 480 600v...
Страница 26: ...25 CONTROL CONSOLE COMPONENTS HAND TILT 44 45 43...
Страница 28: ...27 CONTROL CONSOLE COMPONENTS POWER TILT 41 42 40 44 45 43...
Страница 31: ...30...