1. Introduction
Page 8
105466
– TW-31-E - V1.9 - 06.04.2021
1.8 Technical data of control unit
Operating voltage
230V AC +/-10%, 50 Hz
Relay contacts
3 performance relays
max. switching current
1 x each 6A AC1 bei 250V AC
2 x each 10A AC1 bei 250V AC
max. current per terminal
12A - 250V AC
max. switching voltage
250V AC - 50..60 Hz
Display
13 mm LED display, 4 digits
Display range
-999 .. 9999
Switching status displays
3 mm LED
Number of sensor
1 or 2
Measurement range
-5° .. +95°C
Temperature resolution
0,1°C
Sensor input
for KTY 81-210 (optionally PT-100)
Water detection
via independent level monitor
Digital inputs
- for 230 V
- for low voltage
6 (via optocoupler)
6 (via optocoupler)
Interface
2x RS-485
1xx USB master (for USB stick only)
Connection
Plug-in screw connections
for cables up to 2.5 mm²
Housing
- Dimensions (LxBxH)
- Material
305 mm x 225 mm x 120 mm
Housing and cover ABS (UV-resistant)
screws PA
Protection
IP 65 (DIN EN 60529)
Electrical safety
Protection class II,
Overvoltage category III, pollution degree I
Environment specifications:
- Operation temperature
- Storage temperature
- max. humidity 75% (no dew)
0° .. +50°C
-20° .. +70°C
75% (no dew)
Technical data subject to change.