8. Other informations
105466
– TW-31-E - V1.9 - 06.04.2021
Page 67
8.12.1 Cancellation of the recorded temperatures in the diagram
The agitator-monitoring modules memorize the data recorded by the agitator motors
and evaluate if the milk creates a counter pressure for the agitator.
If the cancellation of this data is required (e.g. exchange of an agitator motor) pro-
ceed as follows:
Select parameter [H71]
Set value 5 -> store
Select parameter [H71] again
Set the original value (depending on configuration) -> store
The tank monitor requires about 4 days for the assimilation of the new motor data.
8.13 Test functions
8.13.1 Test alarm F99
The function “test alarm” is required to test the impacts of an error on the parame-
terized outputs in the F-parameters (relays, SMS etc.).
Method:
Set and store the configuration to be tested in parameter [F99]
Trigger test errors by pressing buttons SET and ARROW UP simultaneously for
four seconds
Check if the required reaction has taken place
Reset the error triggered with the reset button
8.13.2 Function test "Do-Not-Load LED" and "external alarm light"
Used to test the function of the red "Do-Not-Load LED" and the associated relay
contact "external alarm light".
Method:
Hold the "Reset button" for approx. 4 seconds:
For approx. 10 seconds, the red "Do-Not-Load LED" is switched on and the relay
"external alarm light" is energized.