7. Setting of parameters
Page 44
105466
– TW-31-E - V1.9 - 06.04.2021
7.3
Level “General tank monitor parameters” (h parameters)
Detection of the operation mode (see section 4.3)
Range
Def.
h1 Mode detection “cooling”
0 = permanent signal from the cooling tank control
(cooling active)
1 =
Activation by trigger signal “cooling activated”
(see box), end by starting the cleaning cycle
2 = same as 1 + end-detection in case of a temperature
increase and trigger signal “cooling activated” is
longer detected (see section 8.1)
0 .. 2
1
h2
Additional detection “cooling” by
“first milk comes into the tank”
(see section 8.2)
If the cooling was not started at the tank, the start of
mode detection „cooling” takes place by the first milk
feeding.
0 = deactivated
1 = activated (triggered) only in case of a change in
temperature
2 = activated (triggered) directly on the input signal
(milk pump, plate cooling signal etc.)
3 = 1 and 2 in combination
0 .. 3
0
h4
Mode detection “cleaning”
(see section 8.3)
0 = permanent signal from the tank control
(cleaning active)
1 = Activation by signal “open cold water valve” end
by time [h5]
2 = same as 1 + with extension of time when detecting
agitator [h5+h6]
0 .. 2
2
h5 Minimum period cleaning cycle
after signal “open cold water valve”
1..999 min.
30
h6 Extension of time cleaning cycle after [h5]
Setting of time for the extension of the cleaning cycle if
during time [h5] a new “open cold water valve” or an agi-
tator start is detected.
1..30 min.
15
Switch to level
“General tank monitor parameters”
see section 7.2
H parameters
Code: 4711
General tank monitor parameter
Code: 4711
Extended tank monitor parameter
Code: F94A
Alarm configuration
Code: FFFF
Hardware configuration
Code: A384
Sensor adjustment
Code: C212
Service parameter
Code: EA03
I/O test parameter
Code: 10E5
Working level
h1: Trigger signal
„cooling activated“
can take place by:
- Compressor ON
- Ice water pump ON
- Evaporator valve ON