7. Setting of parameters
105466
– TW-31-E - V1.9 - 06.04.2021
Page 45
to section 7.3:
Level “General tank monitor parameters” (h parameters)
Fault
Range
Def.
h10 Water detection in cleaning pipe after end
of cleaning
0 = deactivated
1 = activated
Level electrode in cleaning pipe has to be con-
nected to “level 1”
F45
0 .. 1
0
H11 Monitoring motor protection cooling
0 = deactivated
1 = high active (error, if no signal at the input)
2 = low active (error, if no signal at the input)
F53
0 .. 2
0
Error messages during cooling
Fault
Range
Def.
No cooling start after milk feed...
(see section 8.2)
h17 ... first warning after time [h17]
F17 0..120 min. 30
h18 ... second warning after time [h18]
F18 0..120 min. 45
h19 ... third warning after time [h19]
F19 0..120 min. 60
h20 Target temperature first milking (see 8.5)
Alarm is activated if this temperature has not
been achieved within time [h21] after the start of
the cooling mode.
F20
0..30°C
6,0
h21 Max. time to achieve target temperature
Alarm is activated if this temperature has not
been achieved within time [h20] after the start of
the cooling mode.
0: deactivated
1…999: Time limit in minutes
0..999 min. 180
h23 Milk temperature too high for too long
Function see section 8.4.
F23
0..30,0 °C
10,0
h24 Time limit for [h23]
0: deactivated
1…999: Time limit in minutes
0..999 min.
180
h25 Maximum overtemperature with direct
activation of alarm
Monitoring start when target temp. has been
achieved [h20]
F25
0..30,0 °C
25,0
h27 Milk temperature too low for too long
F27
0..30,0 °C
2,0
h28 Time limit for [h27]
0: deactivated
1…999: Time limit in minutes
0..999 min
120
h29 Alarm in case of exceeding the temperature
with direct alarm activation
F29
0..30,0 °C
0,5
In [h23] an overtempera-
ture alarm can be de-
fined, that activates an
informative (pre-)-alarm
contrary to the critical
faults F1 - F3.
Additional information on the errors see section 6.5.2