What to do if ...?
8
The faults recognised by the controller
are displayed with a fault code and
can be assigned or rectified here.
Fault
codes
1
The fault code display is reset by
confirming with
Yes
.
Fehler
Code
löschen
No
Code
Description
Cause
Rectification
1
∆
T between TKO and TSU or TPU
Pump defective
Repair, or if necessary replace
longer than 15min. >80K
pump
Micro-fuse defective
Replace fuse, rectify fault
Air in system
Vent system
Sensor defective
Replace sensor
Note:
After 15 minutes the solar pump is switched off. If the temperature differential is not maintained, the solar pump
switches on again. The fault message remains saved and can be reset via
Delete fault codes
.
2
∆
T between TK2 and TSU or TPU
Pump defective
Repair, or if necessary replace
longer than 15min. >80K
pump
Micro-fuse defective
Replace fuse, rectify fault
Air in system
Vent system
Sensor defective
Replace sensor
Note:
After 15 minutes the solar pump is switched off. If the temperature differential is not maintained, the solar pump
switches on again. The fault message remains saved and can be reset via
Delete fault codes
.
4
Collector sensor TKO has short or
Sensor or cable
Check installation, if necessary
open circuit
short or open circuit
replace sensor
Note:
The solar pump switches off, if the frost protection function is not active. Otherwise the pump runs at minimum
speed.
Once the cause of the fault has been rectified, the fault message is automatically reset.
5
Collector sensor TK2 has short or
Sensor or cable
Check installation, if necessary
open circuit
short or open circuit
replace sensor
Note:
The solar pump 2 switches off, if the frost protection function is not active. Otherwise the pump runs at minimum
speed.
Once the cause of the fault has been rectified, the fault message is automatically reset.
6
Tank sensor bottom TSU has
Sensor or cable
Check installation, if necessary
short or open circuit
short or open circuit
replace sensor
Note:
The solar pump switches off.
Once the cause of the fault has been rectified, the fault message is automatically reset.
7
Calorifier sensor bottom TPU has
Sensor or cable
Check installation, if necessary
short or open circuit
short or open circuit
replace sensor
Note:
The solar pump switches off.
Once the cause of the fault has been rectified, the fault message is automatically reset.
8.1 Fault messages (fault display)