65
6
Note:
D
Di
if
ff
f.
.
O
OF
FF
F
is a size that can be used to
include the ratings losses.
Change setting continued
Selection, which criteria is used to
load the storage tank cascade.
(
➭
Ch. 7.12)
Variation: 4…6, 8…11, 19, 21, 24…27,
35…38, 51, 52, 84
Setting range:
0…3
Presetting:
0
Priority
solar
loading
0
Temperature differential between return
sensor (THR) and calorifier sensor “top”
(TPO), at which the three way valve
(VRA) is deactivated.
Variation: 9…11, 15, 16, 19, 27, 31, 34,
38, 42, 45,49, 56, 59, 62, 65
Setting range:
0 K…40 K
Presetting:
2.0 K
Return
diff.
Off
2.0K
Temperature differential between return
sensor (THR) and calorifier sensor “top”
(TPO), at which the three way valve
(VRA) is activated.
Variation: 9…11, 15, 16, 19, 27, 31, 34,
38, 42, 45,49, 56, 59, 62, 65
Setting range:
0 K…40 K
Presetting:
5.0 K
Return
diff.
On
5.0K
Swim. pool temperature setpoint leads
to the shutdown of swim. pool loading.
In conjunction with the sensors TSU,
TSB and TPU this setpoint is the
criteria for the continued switching of
the loading.
Variation:
20, 21, 52
Setting range:
0°C…90°C
Presetting:
30°C
Swim pool
temp.
Setpoint
30°C
The pump speed control attempts to
hold the collector temperature higher
than the temperature at sensor TSB
by the control differential set.
(
➭
Ch. 7.5).
Variation:
20, 21, 52
Setting range:
0…40 K
Presetting:
15K
Swim. pool
control
diff.
15.0K
Achieveable max. swimming pool
temperature. Once this temperature is
reached, the
solar pump is switched off, if the passive
collector protection is switch off
(Setting collector protection: 0, 2 or 4).
Variation:
20, 21, 52
Setting range:
20°C…95°C
Presetting:
35°C
Swim. pool
temp.
maximum
35°C
Temperature differential between
collector sensor (TKO) and swim. pool
sensor (TPU) as switch off criteria of
the solar pump.
Variation: 20, 21, 52
Setting range:
0K…40K
Presetting:
4.0K
Swim. pool
diff.
Off
2.0K
Achieveable max. swimming pool
temperature. Once this temperature is
reached, the
solar pump is switched off, even if the
passive collector protection is switch
on. (Setting collector protection: 1, 3
or 5).
Variation:
20, 21, 52
Setting range:
20°C…95°C
Presetting:
40°C
Swim. pool
temp.
protection
40°C