3.3 Commissioning
3.4 Electrical connection
Terminal rail left (sensor)
Terminal rail right (outputs / voltage supply)
Procedure:
1. Select hydraulic variation required.
➭
Ch. 4
2. Carry out electrical connection in accordance with
the hydraulic variation selected.
➭
Ch. 3.4; Ch. 4
3. Program the controller, if necessary, start with
language selection.
➭
Ch. 6.10
4. Set the hydraulic variation selected under item one in
the controller.
➭
Ch. 6.3
5. Activate overheat protection (recommendation).
➭
Ch. 6.8
6. Activate other options as required where possible.
➭
Ch. 6.8
7. Set time and timer programs
➭
Ch. 6.3 … Ch. 6.6
8. Select all temperatures and values and check their
plausibility.
➭
Ch. 6.2
9. Test and check all outputs in type of operation
Manual
(the pump start of the solar pumps is not possible
above collector temperatures of 130°C, not even in
manual operation).
➭
Ch. 6.7
10.Reset controller to type of operation
Auto
.
➭
Ch. 6.1
11.Complete commissioning log in appendix.
12.Show customer the operation and functions of the
controller.
The WRSol 2.0 is constructed in such a way, that the
function of the controller and the type of setting
parameters can be set by selecting the relevant hydraulic
variation.
Only the selection menus and setting parameters required
for the hydraulic variation selected will then be displayed.
All other parameters are blanked out.
Connection
➭
Remove terminal rail cover.
➭
Connect
• sensor lines,
• MFA output,
• pump or change-over valve,
• voltage supply
according to the hydraulic variation installed
(Ch. 4).
➭
Secure all connected cables with the traction reliefs
supplied.
➭
Apply voltage, if fault message appears check sensor
connection, if necessary adjust hydraulic variation.
➭
Refit terminal rail cover once the relevant cable cut-outs
have been opened, use screws (traction relief)
supplied.
Improper installation or repair attempts can
cause life-threatening conditions through
electric shock. The installation must only be
carried out by an electrician with the relevant
qualifications.
The unit and accessories must not be opened.
Repairs must only be carried out by the
manufacturer.
Voltage surge protection
The sensors connected do not require voltage surge
protection.
The flow and return of the solar system must be earthed.
DANGER