![Weishaupt WRSol 1.0 Скачать руководство пользователя страница 16](http://html.mh-extra.com/html/weishaupt/wrsol-1-0/wrsol-1-0_manual_953375016.webp)
16
4
MFA
eBus
TKO
PS
TKV*
TPU
TPO
PS
VIZ*
TSO
PPS
TKO
TSO
TPU
TPO
VIZ*
TKR*
TKR*
TKV*
PPS
X1:
N
1
N
2
N
3
N
4
5
6
X2:
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
PZW*
PZW*
VSP
MFA
TSU
e-Bus
TKO
PS
TWT
TSU
TPU
PS
PWT
M
TPU
PWT
TWT
X1:
N
1
N
2
N
L
3
N
4
5
6
X2:
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
TKO
VSP
AB
B
A
VIZ*
TKR*
VIZ*
TKR*
•
Energy yield calculation (optional;
➭
Ch. 7.10)
•
Circulation function (optional;
➭
Ch. 7.15)
The WRSol 2.0 determines the temperature differential
between the collector sensor (TKO) and the reference
sensor (TPU). If a collector flow sensor (TKV) is
fitted this can be included into the control.
As soon as the temperature differential is greater than the
value set (
C
Ca
al
lo
or
ri
if
fi
ie
er
r
D
Di
if
ff
f.
.
O
On
n
), the solar pump is
switched on and the tank is topped up, until the switch off
condition (
C
Ca
al
lo
or
ri
if
fi
ie
er
r
T
Te
em
mp
p.
.
O
Of
ff
f
) or the maximum
temperature of the storage tank has been reached.
Depending on the average pump speed and the minimum
storage tank temperature, the external heat exchanger can
be blocked via the potential free
Multi-funct. Output
(MFA).
In addition an 18 hour block can be activated.
The DHW function (Ch. 7.14) can also influence the MFA
output.
By adding cold water the warm water from the DHW tank
is transferred into the dual stratification tank.
Using the charge reversal pump calorifier-tank (PPS) the
energy stored is transferred depending on the calorifier
temperature (TPO) and the storage tank temperature
(TSO) (
➭
Ch. 7.19).
Possible settings MFA output:
0, 1, 2, 5, 6, 7, 8, 9, 10, 11, 12
•
Energy yield calculation (optional;
➭
Ch. 7.10)
•
Three way valve
The WRSol 2.0 determines the temperature differential
between the collector sensor (TKO) and the reference
sensor (TSU, TPU).
As soon as the temperature differential is greater than the
value set (
... Diff. On
), the solar pump is switched on
and the tank is loaded.
Once the (
... Temp. Setpoint
) is reached, the three
way valve changes over and and loads the DHW storage
tank provided, in accordance with the priority setting (
➭
Ch. 7.12).
If loading is on sensor TSU, pump PWT runs at lowest
speed (30%), until the storage tank setpoint temperature
has been reached at sensor TWT.
Depending on the average pump speed and the minimum
storage tank temperature, the external heat exchanger can
be blocked via the potential free
Multi-funct. Output
(MFA).
In addition an 18 hour block can be activated.
The DHW function (Ch. 7.14) can also influence the MFA
output.
By adding cold water the warm water from the DHW tank
is transferred into the dual stratification tank.
Possible settings MFA output:
0, 1, 2, 5, 6, 7, 8, 9, 10, 11, 12
KW
WW
Variation 7: Storage tank sequence switching for DHW and retrieval function
* optional
WW
KW
Variation 8: Storage tank cascade for DHW via plate heat exchanger and calorifier
* optional