30
4
MFA
X1:
N
1
N
2
N
L
3
N
4
5
6
TKR*
TSU
eBus
TKO
PS
TSU
TKR*
VIZ*
TPU
PS
M
VIZ*
TPU
PPS
VSP
VSP
TKO
PFK
PFK
TFK
TFK
TSO
TSO
TPO
PPS
TPO
TV
AB
B
A
X2:
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
•
Three way valve
•
Energy yield calculation (optional;
➭
Ch. 7.10)
The WRSol 2.0 determines the temperature differential
between the collector sensor (TKO) and the reference
sensor (TSU, TPU). As soon as the temperature differential
is greater than the value (
... Diff. On
) set, the solar
pump is switched on and the storage tank is loaded.
Once the
... Temp. Setpoint value
has been
reached the three way valve switches over and loads the
calorifier provided according to the priority setting
(
➭
Ch. 7.12).
With the calorifier - tank pump (PPS) the energy stored in
the calorifier is transferred, depending on the storage tank
temperature top (TSO) and the calorifier temperature top
(TPO) (
➭
Ch. 7.17).
Release of solid fuel boiler pump (PFK) (
➭
Ch. 7.7).
The thermal mixer valve (TV) enables fast heat up of the
solid fuel boiler.
Depending on the average pump speed and the minimum
storage tank temperature, the external heat exchanger can
be blocked via the potential free
Multi-funct. Output
(MFA).
In addition an 18 hour block can be activated.
The DHW function (
➭
Ch. 7.14) can also influence the MFA
output.
Possible settings MFA output:
0, 1, 2, 5, 6, 7, 8, 9, 10, 11, 12
Variation 36: Storage tank cascade for DHW with collector and solid fuel boiler via retrieval function
* optional
WW
KW
MFA
X1:
N
1
N
2
N
L
3
N
L
4
5
6
TSU
eBus
TKO
PS
TSU
TKR*
VIZ*
TPU
PS
M
VIZ*
TPU
VBY
VSP
VSP
TKO
PFK
PFK
TFK
TFK
M
TBY
TKR*
TBY
TV
B
AB
A
VBY
AB
B
A
X2:
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
•
Three way valve
•
Energy yield calculation (optional;
➭
Ch. 7.10)
The WRSol 2.0 determines the temperature differential
between the collector sensor (TKO) and the reference
sensor (TSU, TPU).
As soon as the temperature differential is greater than the
value (
... Diff. On
) set, the solar pump is switched on
and the storage tank is loaded. The three way valve (VBY)
is switched over depending on the collector temperature
(TKO ) and the reference sensor (TBY).
Once the (
... Temp. Setpoint value
) has been
reached the three way valve switches over and loads the
calorifier provided according to the priority setting
(
➭
Ch. 7.12).
Release of solid fuel boiler pump (PFK) (
➭
Ch. 77).
The thermal mixer valve (TV) enables fast heat up of the
solid fuel boiler.
Depending on the average pump speed and the minimum
storage tank temperature, the external heat exchanger can
be blocked via the potential free
Multi-funct. Output
(MFA).
In addition an 18 hour block can be activated.
The DHW function (
➭
Ch. 7.14) can also influence the MFA
output.
Possible settings MFA output:
0, 1, 2, 5, 6, 7, 8, 9, 10, 11, 12
Variation 37: Storage tank cascade for DHW and heating with collector/bypass and solid fuel boiler
* optional
WW