Setting for amount of fluid throughput
per impulse of the volume impulse
meter. The volume impulse meter must
be activated in options with
Yes
(
➭
Ch 6.8).
Variation:
1…8, 12…14, 17, 18, 20, 21, 35…37,
40, 41, 43, 44, 52…55, 57, 58, 60, 61,
63, 64, 72, 76…84
Setting range:
0.01…10.0 l/Impulse
Presetting:
0.25 l/Impulse
Through
put
0.25l/I
Change setting continued
The factor depends on the type and the
mixing ratio of heat exchanger fluid.
This factor is used for the energy yield
calculation.
Variation: 1…45, 50…84
Setting range:
0.01…10.0 kJ/lK
Presetting:
3.73 kJ/lK (at 60°C)
Heat
capacity
kJ/lK
3.73
Value set or read at throughput limiter,
at 100% pump rating.
Variation: 22…45, 50…84
Setting range:
0.1…500.0 l/m (litres/minute)
Presetting:
1.5 l/m
Volume
flow
1.5l/m
Value set or read at throughput limiter,
at 100% pump rating of second solar
pump.
Variation: 22…34, 50, 74
Setting range:
0.1…500.0 l/m (litres/minute)
Presetting:
1.5 l/m
Volume
flow2
1.5l/m
The solar pump switches on, when the
collector sensor value reaches the set
value.
The pump switches off, when the
value set is exceeded by 3K
(hysteresis).
Hysteresis: 3K (fixed cannot be altered)
Variation: 1…45, 50…84
Setting range:
–50°C…–41°C ; frost prot. deactivated
–40°C…+20°C ; frost prot. activated
Presetting:
–50°C
Attention:
With variation 20, frost protection should not
be set below 5°C or frost protection should be
deactivated if using a suitable collector fluid
to protect the heat exchanger.
Note:
With sensor short circuit, the pump is driven
at
PS Speed Minimum
, if the frost protection
temperature > –40°C has been set.
Frost
protection
-50.0°C
Lowest limit value of modulation range
of PWT pump to plate heat exchanger.
Variation: 3, 8, 11, 63…65, 84
Setting range:
10…100%
Presetting:
30%
PWT
Speed
Minimum
30%
Temperature differential between
collector sensor (TKO) and tank sensor
(TSU) as switch on criteria of solar
pump.
Variation: 1…6, 8…11, 17…19,
21…27, 32…38, 43…45,
50…59, 84
Setting range:
0 K…40 K
Presetting:
7.0 K
Tank
diff.
On
7.0K