IE-CS(T)-2TX-xRS232/485
Web Console Configuration
5-22
ATTENTION
The
Destination IP address
parameter can use both IP address and Domain Name. For some applications,
the user may need to send the data actively to the remote destination domain name.
Designated Local Port 1/2/3/4
Setting
Factory Default
Necessity
TCP Port No.
5011 (Port 1)
5012 (Port 2)
5013 (Port 3)
5014 (Port 4)
Required
Connection control
Setting
Factory Default
Necessity
Startup/None, Any
Character/None,
Any Character/Inactivity Time,
DSR ON/DSR OFF, DSR ON/None,
DCD ON/DCD OFF, DCD ON/None
Startup/None Required
The meaning of each of the above settings is given in the table below. In general, both the Connect condition
and Disconnect condition are given.
Connect/Disconnect
Description
Startup/None
(default)
A TCP connection will be established on startup, and will remain active indefinitely.
Any Character/None
A TCP connection will be established when any character is received from the serial
interface, and will remain active indefinitely.
Any Character/
Inactivity Time
A TCP connection will be established when any character is received from the serial
interface, and will be disconnected when the Inactivity time out is reached.
DSR On/DSR Off
A TCP connection will be established when a DSR “On” signal is received, and will
be disconnected when a DSR “Off” signal is received.
DSR On/None
A TCP connection will be established when a DSR “On” signal is received, and will
remain active indefinitely.
DCD On/DCD Off
A TCP connection will be established when a DCD “On” signal is received, and will
be disconnected when a DCD “Off” signal is received.
DCD On/None
A TCP connection will be established when a DCD “On” signal is received, and will
remain active indefinitely.