4 Module descriptions
| Technical Data
15
2599890000/01/03.2020
Manual UR67-PROFINET-V14
Technical data
UR67-PN-V14-CU-16DI-12
(2599680000)
UR67-PN-V14-CU-8DIDO-12
(2599670000)
UR67-PN-V14-POF-16DI-12
(2599700000)
UR67-PN-V14-POF-8DIDO-12
(2599690000)
Current limitation response time
< 100 µs
Surge protection
yes
Supply
Sensor/module supply U
S1
24 V DC +20% / -15%
Actuator supply U
S2
24 V DC +20% / -15%
Module electronics current con-
sumption
< 150 mA at 24 V DC
Test voltage
500 V DC between current paths and to FE
Functional safety
Actuator supply U
S2,
reliable cutout in accordance with PL d
Voltage bypass
10 ms
General data
Type of protection
IP 67 (not UL-tested)
Enclosure material
Die-cast zinc, matt nickel surface
Temperature
Operation
-20 ... +55 °C
Storage, transport
-40 ... +70 °C
Weight
965 g
970 g
995 g
1000 g
Dimensions (H × W × D)
43 × 60 × 225 mm
51 × 60 × 225 mm
Flammability rating
UL 94
Air pressure
Operation
1013 hPa (height: 0 m) up to 700 hPa (height: 3000 m) in accordance with IEC 61131-2
Storage, transport
1013 hPa (height: 0 m) up to 700 hPa (height: 3000 m) in accordance with IEC 61131-2
Humidity
10% to 95%, non-condensing in accordance with DIN EN 61131-2
Vibration resistance
0.35 mm / 10 ... 60,1 Hz and 5 g / 60,1 ... 500 Hz in accordance with DIN EN 60068-2-6
Shock resistance
50 g / 11 ms in accordance with DIN EN 60068-2-27
Pollution degree
3 (in accordance with EN 60664-1, VDE 0110-1)
Overvoltage category
II
Tightening torques
Mounting screw M6
3 Nm
Earthing screw M4
1.2 Nm
Plug connector M12
0.5 Nm
M12 protective cap
0.5 Nm
Approvals and standards
EMC
EN 61000-6-2:2005/AC:2005,
EN 61000-6-4:2007/A1:2001