PROFINET
The GSDML file is available from WEG website (http://www.weg.net). It is important to note if the GSDML configuration
file is compatible with the firmware version of the SRW01-ETH smart relay.
8.7
MODBUS TCP CONNECTIONS
The device for PROFINET IO also provides up to 2 Modbus TCP connections. These connections can be used for
parameterization, as well as access to markers and data used for SRW01-ETH ladder programming. The available
Modbus functions and communication data are described in item 6.
8.8
STARTUP GUIDE
Next it describes the main steps for commissioning SRW01-ETH smart relay on Ethernet network using the PROFINET
protocol. These steps represent an example of use. Refer to specific chapters for details on the steps.
8.8.1
Installing the Product on an Ethernet Network
1. Connect the Ethernet cable to the device, considering the necessary care in network installation, as described
in section 4:
Use shielded cable.
Properly ground the network devices.
Avoid laying communication cables next to power cables.
8.8.2
Configuring the Drive
1. Follow the recommendations described in the user’s manual to program the related to device settings, motor
parameters, desired functions for I/O signs, etc..
2. Program command sources as desired for application.
3. Program communication parameters such as Station Name, etc.
4. Set the desired action for communication errors, through the P0313.
5. Set number of I/O words as well as the contents of each word using parameters P0800 to P0819 and P0850
to P0869.
6. If necessary, restart the Ethernet interface using P0899.
8.8.3
Configuring the Master
The way you do the network setup depends largely on the master and the configuration tool. It is important to know
these tools to perform this activity. In general, the following steps are required to do the network configuration.
1. Load the GSDML file
2
to the list of devices in the network configuration tool.
2. Select SRW01-ETH smart relay from the available list of devices on the network configuration tool. This can be
done manually or automatically, if allowed by the tool.
3. For the master configuration, you must indicate the number of I/O words exchanged with the master. It is
necessary to select word by word, first selecting all input words and then all output words.
2
The GSDML file is available from WEG website (http://www.weg.net). It is important to note if the GSDML configuration file is compatible with
the firmware version of the SRW01-ETH smart relay.
SRW01-ETH | 33