Programming
Table 5.2:
P0680 indications
Bit
Value/Description
Bit 0
Error
0
: the relay is not in error condition.
1
: the relay is in error condition.
Note: The error number can be read via the parameter P0016 – Current Error.
Bit 1
Trip
0
: the relay is not in the trip condition.
1
: the relay is in the trip condition.
Note: The trip fault number can be read via the parameter P0016 – Current Error.
Bit 2
Alarm/Fault
0
: the relay is not in the alarm/fault condition.
1
: the relay is in the alarm/fault condition.
Note: The alarm/fault number can be read via the parameter P0016 – Current Error.
Bit 3
Motor On
0
: motor Off.
1
: Motor On.
Bit 4
Remote Mode
0
: the relay is in local mode.
1
: the relay is in remote mode.
Bit 5
Digital Input I11 Status
0
: I11 digital input is deactivated.
1
: I11 digital input is activated.
Bit 6
Digital Input I12 Status
0
: I12 digital input is deactivated.
1
: I12 digital input is activated.
Bit 7
Digital Input I13 Status
0
: I13 digital input is deactivated.
1
: I13 digital input is activated.
Bit 8
Digital Input I14 Status
0
: I14 digital input is deactivated.
1
: I14 digital input is activated.
Bit 9
Digital Input I15 Status
0
: I15 digital input is deactivated.
1
: I15 digital input is activated.
Bit 10
Digital Input I16 Status
0
: I16 digital input is deactivated.
1
: I16 digital input is activated.
Bit 11
Digital Output O1 Status
0
: O1 digital output is deactivated.
1
: O1 digital output is activated.
Bit 12
Digital Output O2 Status
0
: O2 digital output is deactivated.
1
: O2 digital output is activated.
Bit 13
Digital Output O3 Status
0
: O3 digital output is deactivated.
1
: O3 digital output is activated.
Bit 14
Digital Output O4 Status
0
: O4 digital output is deactivated.
1
: O4 digital output is activated.
Bit 15
Reserved.
P0682 – CONTROL WORD
Range:
0000h ... FFFFh
Default:
0000h
Properties:
RW
Description:
It is the the smart relay Ethernet interface control word. This parameter can only be changed via Ethernet interface.
For the other sources (HMI, etc.) it behaves like a read-only parameter.
Actually, it represents the control word itself, whose data format varies according to the chosen operation mode
(P0202).
Each bit of this word represents a command that can be executed.
Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Function
Reserved
Digital
O
utput
O8
V
alue
Digital
Output
O7
V
alue
Digital
Output
O6
V
alue
Digital
Ou
tput
O5
V
alue
Digital
Output
O4
V
alue
Digital
Output
O3
V
alue
Digital
Outp
ut
O2
V
alue
Digital
Output
O1
V
alue
Remote
Reset
Command
3
Command
2
Command
1
SRW01-ETH | 14