Programming
5
PROGRAMMING
Next, the SRW01-ETH smart relay parameters related to the Ethernet communication will be presented.
5.1 SYMBOLS FOR THE PROPERTIES DESCRIPTION
RO
Read-only parameter
RW
Read-write parameter
Sys
System parameter, its value is updated when the ”PROG” key is pressed.
CFG
Configuration parameter, it can be changed with motor stopped only
P0029 – VALUE OF ADDRESSING SWITCHES
Range:
0 to 255
Default:
-
Properties:
RO
Description:
It presents the addressing switch value identified at the power-up of the smart relay.
The two addressing switches, close to the SRW01-ETH Ethernet connectors, allow to program the expected IP
address or Station Name.
In order to obtain information about the possible configurations with switches, refer to item 4.1.
P0313 – ACTION IN CASE OF COMMUNICATION ERROR (FIELDBUS)
Range:
0 = Only Fault Indication
1 = The motor is turned off
2 = Motor is turned off and commands are reset
3 = It changes to Local
Default:
0
Properties:
RW, Sys
Description:
It allows the selection of the action to be executed by the device, if it is controlled via network and a communication
error is detected.
Table 5.1:
P0313 options
Option
Description
0 = Only Fault Indication
Fault indication only with no action taken. The indication of fault will be automatically
removed if the fault condition is cleared and the relay status are not either Trip or Error. If
the relay status is Trip or Error, it is mandatory to perform “error reset” in order to remove
the fault indication.
1 = The motor is turned off
It switches the motor off, for the operation modes where this commands exists. It is
necessary to perform the error reset in order to remove the indication.
2 = Motor is turned off and
commands are reset
It switches the motor off and resets the commands. It is necessary to perform the error
reset in order to remove the indication.
3 = It changes to Local
It changes to local mode, providing that the local/remote selection is programmed to
be executed via Fieldbus. The indication of fault will be automatically removed if the
fault condition is cleared and the relay status are not either Trip or Error. If the relay
status is Trip or Error, it is mandatory to perform “error reset” in order to remove the fault
indication.
The following events are considered communication errors:
SRW01-ETH | 12