Webasto BlueCool Classic Series
TROUBLESHOOTING
29
Table 5
Failure
code
Description
Possible cause
Solution
<AAA> Low Voltage
Low voltage cut-out. Power
supply was over 5 sec lower than
controller setting. Probably
caused by long length power
supply cable or overload.
Check setting, default 195 V.
Don't set below 195 V to avoid
damages to the compressor or to
expire warranty.
Improve power supply.
<A01>
Low pressure cut-out
compressor 1
(Classic > 20,000
BTU)
Defective pressure sensor or
open/short circuit.
Check wiring or replace pressure
sensor on Schrader valve.
COOLING MODE:
Insufficient air flow.
Check air flow.
Δ
T evaporator in/out minimum
4K.
HEATING MODE:
Insufficient seawater flow or
seawater too cold (temperature
below 6 °C or 43 °F).
Blocked sea-water strainer or not
primed.
Check discharge water volume.
V= 8 l/min
(or > 30,000 BTU V= 18 l/min).
Δ
T in/out minimum 4K.
When T seawater < 4 °C:
preheating necessary.
Clean strainer and bleed seawater
circuit.
Lack of refrigerant.
Refrigerant leak check.
<A02>
High pressure cut-out
compressor 1
Defective pressure sensor or
open/short circuit.
Check sensor and wiring. Replace
sensor on Schrader if necessary.
COOLING MODE:
Insufficient seawater cooling.
Blocked seawater strainer or not
primed.
Check discharge water volume.
V= 8 l/min
(or > 30,000 BTU V= 18 l/min).
Clean strainer and bleed sea-
water circuit.
HEATING MODE:
Insufficient air flow.
Check air-flow.
Δ
T evaporator in/out minimum
4K.
<A03>
to
<A08>
Not used for BlueCool Classic units.
<A09>
Cabin temperature
sensor failure
Broken external temperature
sensor, open/short circuit, not
present or programmed wrong.
Replace sensor or controller.
<A10>
Evaporator
temperature sensor
failure.
Defective evaporator sensor or
open/short circuit.
Check wiring or replace sensor.
Water infiltration (condense) can
cause a read-out deviation or
erratic functioning before an error
code occurred.
<CA11> All compressors
manually off.
Compressor(s) programmed not
active in controller setting.
Check settings. At least one
compressor should be
programmed active.
C01=ON
C00=OFF
<bA11> Fan standby.
Blower operation from TCC card
impossible.
Discharge temperature higher
than set point on cooling or
lower on heating.
Run compressor/unit for a certain
time to reach required discharge
temperature.
Blower fan will start and blinking
error code bA11 will disappear
automatically.