PROGRAMMING
Webasto BlueCool Classic Series
24
Code <9>
02
Time delay before restart in minutes after a
compressor stop when in “deicing”
procedure (both for cool and heat cycle).
01 - 99 min.
Code <A>
00
Factory calibration of AC voltage 60 Hz as
displayed on the digital panel when accessing
the secondary commands by the
key.
Adjustment range:
between -30 and +20
Volt.
Code <b>
5.20
Program version
5.**
Code <c>
00
Pump <0> outlets on the TCC controller card
non-regulated for standard 115V / 230V
seawater pump.
For the use of the
WEBASTO WB200
self-priming variable
speed pump this code
should be set to <1>.
In that case the AC
outlet is pulse hashed
to enable variable
pump speed.
Code <d>
12(V)
Lower adjustment ceiling DC output for
special self-priming pump.
Can be adjusted to
higher ceiling (18V) -
see also Code <E>
hereafter.
Code <E>
18 (V)
Higher adjustment ceiling DC output for
special self-priming pump.
Can be adjusted
downward to lower
ceiling - see also
Code <d> here-
above.
Code <F>
01
Not available
00 - 01
Table 3
Description of Programming Codes - setpoint at 29 °C (84 °F)
Code #
Factory
Setting
Description
Optional Settings