Battery testers should not rely solely on manual
operation or automated scripts for safety. Errors can
subject batteries to overcharging, which can result in
battery damage or fire.
Batteries should be monitored by independent hardware
for one or more of these unsafe conditions:
• Over voltage
• Over temperature
• Excess pressure
• Excess gassing (H2)
The HV Interlock on the 900 EX is provided to allow a
hardware monitor to shut down the 900 EX in the event
of an unsafe battery condition.
Before attempting to service the system, follow these
steps:
1. Turn off the Input Circuit Breaker or Main
Disconnect Switch.
2. Turn off local disconnect on the left side of the
unit.
3. Depress and latch the Emergency Off switch for at
least five (5) minutes to allow the high voltage to
discharge.
4. Do not open the covers; there are no user
serviceable parts inside.
CONTACT WEBASTO’S CUSTOMER SERVICE DEPARTMENT
PRIOR TO PERFORMING ANY SERVICE ON THE UNIT.
1-866-767-4242
Содержание 900EX
Страница 1: ...Installation Operation and Maintenance Manual EV Test Systems 900 EX ...
Страница 6: ...iv ...
Страница 7: ...Chapter 1 Introduction ...
Страница 11: ...Chapter 2 System Description ...
Страница 25: ...Chapter 3 Installation ...
Страница 29: ...Chapter 4 Operation ...
Страница 48: ...42 ...
Страница 49: ...Chapter 5 Maintenance ...
Страница 53: ...Appendix A Glossary of Terms ...
Страница 58: ...52 ...
Страница 59: ...Appendix B DC I O Connector Assembly ...
Страница 63: ...Appendix C 900 EX Remote Voltage Sense Operation ...
Страница 66: ...60 ...
Страница 67: ...Appendix D High Voltage Interlock Wiring ...
Страница 69: ...Appendix E Index ...
Страница 72: ...22855 03 04 ...