background image

 

CLICK 516 

•  USER GUIDE 

7

Note

The RJ-11 jack on the front of the module is the port that needs to connect to the 
Click contact closure cards. 

The second block has a TD and RD for wiring RS-232 communication. The ground for RS-

232 communication is on the first block.

Note

The Click 516 operates at a baud rate of 9600 bps. Make sure the SmartSensor HD is 
set up to operate at 9600 bps.

While the device, as a Click 500 series module, also has two digital inputs ports (first block 

on the bottom) and two digital output ports (second block on the bottom) the standard 

Click 516 application does not use these. The Click 500 series module also has two DIP 

switches on the left side of the module. The DIP switches are used to program or reprogram 

the unit; however, for normal Click 516 operation, all DIP switches should be in the OFF 

position.

Warning

The sixth switch of DIP switch 1 controls the mode of the device. Make sure that 
this switch is in the OFF position. If it gets turned on, the device will enter program-
ming mode and all of the faceplate LEDs will turn off once a serial connection is 
made. To exit programming mode, power will need to be cycled on the device.

Configuration Features

There are three banks of LEDs located on the front of the Click 516.

The yellow and red banks of LEDs display submenu selections and application information. 

(see the Operating Modes section of this chapter for more information).

The system LEDs (multicolored bank in the middle of the module) have dual functions: 

they are activity indicators, reporting system status information, and they are also used in 

selecting operation modes from the main menu.

The blue LED does not have an activity-indicating function. The other three LEDs indicate 

system status as follows:

Содержание Click 516

Страница 1: ...Click 516 USER GUIDE...

Страница 2: ...www wavetronix com 78 East 1700 South Provo Utah 84606 801 734 7200 Click 516 USER GUIDE...

Страница 3: ...CC rules which state that operation is subject to the following two conditions 1 this device may not cause harmful interference and 2 this device must accept any interference received including interf...

Страница 4: ...ent data messages and interval data from a SmartSensor HD Figure 1 The Click 516 The Click 516 operates in the following two states Normal and HIOCC These states are described below Normal State In no...

Страница 5: ...te There are only eight LEDs on the front of the Click 516 This means that only the first eight lanes will be monitored by the Click 516 front panel The LEDs will always come on starting with the firs...

Страница 6: ...hicle speed data to change the duration to greater than 1 9 seconds Once the Click 516 receives an interval where the speed is greater than the threshold the Click 516 will go out of HIOCC mode and al...

Страница 7: ...ule is used to forward data retrieved from the sensor and it is also used to configure the device with Click Supervisor The DB 9 port on the front of the Click 516 is the only port that is active when...

Страница 8: ...operation all DIP switches should be in the OFF position Warning The sixth switch of DIP switch 1 controls the mode of the device Make sure that this switch is in the OFF position If it gets turned o...

Страница 9: ...Click 516 Located on the front of the module below the DB 9 connector is a push button labeled Mode Switch The push button allows you to make selections from the menu see the Op erating Modes section...

Страница 10: ...complete properly Operating Modes The Click 516 has two operating modes Run mode and Device Setup mode These modes are accessed through the mode menu which is controlled via the push button the system...

Страница 11: ...ion The mode will now start running Run Mode blue solid Run mode is the first mode presented in the mode selection process but usually the second one to be used It might first be necessary at least th...

Страница 12: ...a SmartSensor HD and veri fies that the duration field of in the message is greater than 2 3 seconds If it is found to be shorter than 2 3 seconds the duration is change to be 2 3 seconds The Event D...

Страница 13: ...Click Supervisor using the Communication task from the main menu When detected the Click 516 will show up in the device list Highlight the device and press Select and after transferring the necessary...

Страница 14: ...elect the Setup Click task from the main menu and this will give the list of available drivers Select the Expert driver and click OK Figure 6 List of Drivers The driver will load the appropriate infor...

Страница 15: ...e Occupancy threshold that is used along with the Min Speed to determine if the Click 516 should enter HIOCC MODE The Speed of the interval must be below the Min Speed and the Occupancy of the interva...

Страница 16: ...sensor is storing Interval Data This field is read only Time Zone Allows you to select the appropriate time zone Table 3 Description of Sensor Tab Note If any of the read only fields are blank it mea...

Страница 17: ...t LED Solid Reset all settings except Serial Number and XML variable map Second LED Solid Reset all settings except Serial Number After being reset the Click 516 will return to the last mode that it w...

Страница 18: ...Euro Pat Nos 1435036 1438702 1611458 Other US and international patents pending Wavetronix SmartSensor Click Command and all associated logos are trademarks of Wavetronix LLC All other product or bra...

Страница 19: ...www wavetronix com...

Отзывы: