1  General information

1.1  Important information about this manual

NOTICE

The plant operator is responsible for

ensuring compliance with the local laws and regula-
tions (e.g. accident prevention regulations, etc.). 
Incorrect operation or operating the Isomix-F outside 
the specifications invalidates all warranty claims.

This installation and operating manual

•  is an integral part of the Isomix-F

•  contains instructions and information about safe and cor-

rect installation and commissioning of the Isomix

•  must be available to all users throughout the entire service 

life of the Isomix

•  is intended for trained personnel who are familiar with the 

applicable standards and regulations and, in particular, 
with the relevant safety concepts, operation and mainte-
nance of the Isomix

•  is protected by copyright and may not be altered without 

the manufacturer’s permission

1.2  Product conformity

A Declaration of Conformity according to Machinery Directive 
2006/42/EC has been issued for the Isomix-F product.

1.3  Product features

•    All connections to the system have 1" male thread and flat 

sealing

•  Very convenient controls, compact, space-saving design.

Contents

General information ������������������������������� 2

1.1 

Important information about this manual ...................2

1.2 

Product conformity ....................................................2

1.3 

Product features ........................................................2

2 Safety ������������������������������������������������������� 3

2.1 

Presentation of safety information ..............................3

2.2 

Important safety information ......................................3

2.3 

Intended use ..............................................................3

2.4 

Foreseeable misuse ...................................................3

2.5 

Responsibilities of the plant operator .........................3

2.6 

Personnel groups ......................................................3

2.7 

Information on the operating environment .................3

3 Structure �������������������������������������������������� 4

4 Function ��������������������������������������������������� 4

Technical data ����������������������������������������� 4

Overall dimensions ��������������������������������� 5

Pressure loss diagram ��������������������������� 5

Installation and commissioning ������������ 6

8.1 Installation ..................................................................6

8.2 

Mounting in combination with Heat Interface Unit HIU 2

 ..6

8.3 

Temperature limiter ....................................................7

8.4 

Initial commissioning ..................................................7

8.5 

Setting the floor flow temperature .............................7

8.6 

Limiting the floor flow temperature ............................7

9 Troubleshooting �������������������������������������� 8

10 Maintenance �������������������������������������������� 9

10.1  Annual maintenance ..................................................9

10.2  Replacement of wear parts .......................................9

11 Disposal ������������������������������������������������� 10

11.1 

Return to the manufacturer ...................................... 10

11.2    Notification of administrative bodies and the manufacturer .. 10

12 Warranty ������������������������������������������������ 10

Содержание Isomix-F

Страница 1: ...Isomix F Control station for constant maintenance of the flow temperature in surface heating systems Installation and Operating Manual translated from the original operating manual WattsWater eu ...

Страница 2: ...cording to Machinery Directive 2006 42 EC has been issued for the Isomix F product 1 3 Product features All connections to the system have 1 male thread and flat sealing Very convenient controls compact space saving design Contents 1 General information 2 1 1 Important information about this manual 2 1 2 Product conformity 2 1 3 Product features 2 2 Safety 3 2 1 Presentation of safety information ...

Страница 3: ... operated by people including children with limited physical sensory or mental capacities or by people with insufficient experience or previ ous knowledge 2 4 Foreseeable misuse The following is considered to be foreseeable misuse Operating the Isomix F beyond its specifications Improper use of the Isomix F Modifications to the Isomix F that have not been agreed with the manufacturer Use of replac...

Страница 4: ... circuit and thus keeps the flow tem perature constant within a narrow range The actual value can be checked on the thermometer 5 Check valve 6 pre vents a short circuit of the primary circuit The temperature limiter 8 switches off the circulating pump 1 when the supply temperature is exceeded thus prevent ing the panel heating system from overheating 5 Technical data Hydraulic performance data Ma...

Страница 5: ...no 10070292 5 EN ENGLISH 6 Overall dimensions G1 G1 22 5 82 ca 225 ca 98 210 65 5 25 1 Fl 1 Fl Fig 6 1 Overall dimension 7 Pressure loss diagram 1 10 100 1 000 100 1 000 10 000 Fig 7 1 Pressure loss diagram Flow rate l h Pressure loss mbar ...

Страница 6: ...own before carrying out maintenance cleaning and repair work During installation it must be ensured that the cables from the pump and temperature limiter are not damaged or kinked the sensor capillary tube is not damaged or kinked The cables must not be under tension 1 Fit the control station to the manifold with the 1 nuts and associated seals The control station can be fitted on the right or lef...

Страница 7: ...tion of flow until the air and any contamination has been removed from the circuit completely The non return valve 14 in the mixer bypass prevents any short circuit when flushing 10 Repeat the process for all the heating circuits Fig 8 3 Fig 8 4 NOTICE Flushing is permitted only in the direction of flow of the heating circuits i e the water must enter through the flow manifold and come out of the ...

Страница 8: ...open Hot water is injected from the primary heating circuit As a result the control station heats up When the maxi mum temperature of the TL is reached the contact opens The pump does not switch on again Remove TL from the control station and fit to supply heat ing circuit manifold See 1 1 2 Underfloor heating flow temperature cannot be set to the required value or the feed temperature fluctuates ...

Страница 9: ...e seals as required 2 Functional check Check that settings and operating and performance parameters are set correctly Check flow noise during operation Ask users if there are any noticeable problems 3 Action to be taken following maintenance work Check that all screw fittings that were unscrewed have been retightened and retighten if necessary Remove all tools materials and other equipment used fr...

Страница 10: ...omix F properly or commission a spe cialist company to do so 3 Sort the assemblies and component parts into recyclable materials hazardous substances and operating materials 4 Dispose of the assemblies and components in accord ance with local laws and regulations or take them to be recycled 11 1Return to the manufacturer Get in contact with the manufacturer if you would like to return the Isomix F...

Отзывы: