background image

ISOMIX F-IM-DE-W-UK-01-2021-Rev4 | Part no. 10070292

7

EN

ENGLISH

8.3  Temperature limiter

In the event of a fault, the temperature limiter switch-
es off the circulation pump and so avoids overheating 
of the surface heating system�

•  The temperature limiter must be fitted to the supply of the 

heating circuit manifold.

•  Set the temperature on the (optional) temperature limiter to 

approx. 55 °C.

8.4  Initial commissioning

1.  Connect the control station to the pipe network.
2.  Shut off the ball valves (15). 
3.  Switch off the pump and close all of the heating circuits 

on the distributor. 

It is sufficient to close the valves in the return of the 
heating circuit manifold with the protection caps�

4.  Fill the manifold and control station with hot water (in 

accordance with VDI 2035): 

5.  connect the filling hose to the fill and drain valve on the 

return (9b, Fig. 8-3) and the draining hose to the fill and 
drain valve on the supply (9a, Fig. 8-3). 

Heating circuits are closed� 

6.  Open both fill and drain valves and fill the manifold and 

control station until water comes out of the fill and drain 
valve on the supply. Close both fill and drain valves.

7.  To fill and flush the heating circuits, connect the filling 

hose to the supply fill and drain valve (9a, Fig. 8-4) and 
the emptying hose to the return fill and drain valve (9, Fig. 
8-4).
 

8.  Open the heating circuit to be flushed. 
9.  Open fill and drain valve and flush out the heating circuit 

in the direction of flow until the air and any contamination 
has been removed from the circuit completely. 

The non-return valve (14) in the mixer bypass prevents 
any short circuit when flushing�

10. Repeat the process for all the heating circuits.

Fig. 8-3 

Fig. 8-4 

NOTICE

Flushing is permitted only in the direction

of flow of the heating circuits, i.e. the water must enter 
through the flow manifold and come out of the return! 
The drain must always be open, as otherwise the high 
water pressure could damage the heating system.  
The instructions on flushing in the operating manual 
for the heating circuit manifold must also be observed.

8.5  Setting the floor flow temperature

The adjustment handwheel on the thermostat head has a 
scale of 1 - 7 (A, Fig. 8-5 Setting of the supply temperature). 
The set temperature should be taken from the table:

A

B

B

C

Fig. 8-5 Setting of the supply temperature

1

2

3

4

5

6

7

20 °C

28 °C

37 °C

45 °C

53 °C

62 °C

70 °C

8.6  Limiting the floor flow temperature

Flow temperatures above 50 °C are not usually used for sur-
face heating systems. 

The system temperature is often significantly lower than the 
maximum value that can be set on the thermostat head. To 
avoid damage to the floor structure from excess temperature, 
the flow temperature set value can be limited and locked in 
on the thermostat head.

1.  Set the temperature and, with the surface heating run-

ning, check it on the thermometer.

2.  If it is correct, position one of the locking devices (B) 

directly in front of and behind the marking arrow (C).

The setting can also be protected by an additional adjust-
ment lock (accessory: SE 148 GA) to prevent unintended 
actuation.

Содержание Isomix-F

Страница 1: ...Isomix F Control station for constant maintenance of the flow temperature in surface heating systems Installation and Operating Manual translated from the original operating manual WattsWater eu ...

Страница 2: ...cording to Machinery Directive 2006 42 EC has been issued for the Isomix F product 1 3 Product features All connections to the system have 1 male thread and flat sealing Very convenient controls compact space saving design Contents 1 General information 2 1 1 Important information about this manual 2 1 2 Product conformity 2 1 3 Product features 2 2 Safety 3 2 1 Presentation of safety information ...

Страница 3: ... operated by people including children with limited physical sensory or mental capacities or by people with insufficient experience or previ ous knowledge 2 4 Foreseeable misuse The following is considered to be foreseeable misuse Operating the Isomix F beyond its specifications Improper use of the Isomix F Modifications to the Isomix F that have not been agreed with the manufacturer Use of replac...

Страница 4: ... circuit and thus keeps the flow tem perature constant within a narrow range The actual value can be checked on the thermometer 5 Check valve 6 pre vents a short circuit of the primary circuit The temperature limiter 8 switches off the circulating pump 1 when the supply temperature is exceeded thus prevent ing the panel heating system from overheating 5 Technical data Hydraulic performance data Ma...

Страница 5: ...no 10070292 5 EN ENGLISH 6 Overall dimensions G1 G1 22 5 82 ca 225 ca 98 210 65 5 25 1 Fl 1 Fl Fig 6 1 Overall dimension 7 Pressure loss diagram 1 10 100 1 000 100 1 000 10 000 Fig 7 1 Pressure loss diagram Flow rate l h Pressure loss mbar ...

Страница 6: ...own before carrying out maintenance cleaning and repair work During installation it must be ensured that the cables from the pump and temperature limiter are not damaged or kinked the sensor capillary tube is not damaged or kinked The cables must not be under tension 1 Fit the control station to the manifold with the 1 nuts and associated seals The control station can be fitted on the right or lef...

Страница 7: ...tion of flow until the air and any contamination has been removed from the circuit completely The non return valve 14 in the mixer bypass prevents any short circuit when flushing 10 Repeat the process for all the heating circuits Fig 8 3 Fig 8 4 NOTICE Flushing is permitted only in the direction of flow of the heating circuits i e the water must enter through the flow manifold and come out of the ...

Страница 8: ...open Hot water is injected from the primary heating circuit As a result the control station heats up When the maxi mum temperature of the TL is reached the contact opens The pump does not switch on again Remove TL from the control station and fit to supply heat ing circuit manifold See 1 1 2 Underfloor heating flow temperature cannot be set to the required value or the feed temperature fluctuates ...

Страница 9: ...e seals as required 2 Functional check Check that settings and operating and performance parameters are set correctly Check flow noise during operation Ask users if there are any noticeable problems 3 Action to be taken following maintenance work Check that all screw fittings that were unscrewed have been retightened and retighten if necessary Remove all tools materials and other equipment used fr...

Страница 10: ...omix F properly or commission a spe cialist company to do so 3 Sort the assemblies and component parts into recyclable materials hazardous substances and operating materials 4 Dispose of the assemblies and components in accord ance with local laws and regulations or take them to be recycled 11 1Return to the manufacturer Get in contact with the manufacturer if you would like to return the Isomix F...

Отзывы: