background image

4

ISOMIX F-IM-DE-W-UK-01-2021-Rev4 | Part no. 10070292

EN

ENGLISH

3  Structure

1

3

5

8

4

6

2

7

B

D

C

A

Fig. 3-1 Structure

1

Circulation pump 

2

Thermostatic head 

3

3-way mixer valve 

4

Thermowell for capillary tube temperature sensor  

5

Eccentric screw fitting with thermometer

6

Insert check valve

7

Connection for return flow sensor 1/8"(option)

8

Temperature limiter (optional)

A

Primary supply  (1" male thread)

B

Primary return  (1" male thread)

C

Surface heating/cooling supply (1" union nut)

D

Surface heating/cooling return (1" union nut)

4  Function

The mixer valve (3) on the control station is controlled via 
a thermostat head (2) with capillary tube and sensor ele-
ment on the heating circuit supply (A). Deviations from the 
set value immediately cause a valve stroke change, there-
by changing the quantity of hot water injected from the boiler 
circuit accordingly. The water injected mixes with the return 
water from the heating circuit and thus keeps the flow tem-
perature constant within a narrow range. The actual value 
can be checked on the thermometer (5). Check valve (6) pre-
vents a short-circuit of the primary circuit

The temperature limiter (8) switches off the circulating  pump  
(1), when the supply temperature is exceeded, thus prevent-
ing the panel heating system from overheating.

5  Technical data

Hydraulic performance data

Max. operating pressure 

10 bar 

Max. ambient temperature 

40 °C 

Max. operating temperature 

80 °C 

Setting range of supply 

temperature

20 - 70 °C

Kvs value

3,2 m³/h

Heating demand

 14 kW at ∆T=10K

Differential pressure

max. 500 mbar

Media

Water/water-glycol mixture 

as per VDI 2035/ÖNORM 

(Austrian standard) 5195

Connections to pipe network

Primary (heat generator)

1" male thread, flat sealing

Secondary (heat distribution)

1" fl. (union nut), flat sealing

Toques of the fitting

¾"

 35 Nm

1" 

55 Nm

Materials

Fittings

Brass CW617 N, nickel plated

Seals and O-rings

AFM34/2 and EPDM 

Plastics

Impact resistant and tempera-

ture resistant

Circulation pump and temperature limiter

Technical data can be found in the enclosed technical 

documentation.

Содержание Isomix-F

Страница 1: ...Isomix F Control station for constant maintenance of the flow temperature in surface heating systems Installation and Operating Manual translated from the original operating manual WattsWater eu ...

Страница 2: ...cording to Machinery Directive 2006 42 EC has been issued for the Isomix F product 1 3 Product features All connections to the system have 1 male thread and flat sealing Very convenient controls compact space saving design Contents 1 General information 2 1 1 Important information about this manual 2 1 2 Product conformity 2 1 3 Product features 2 2 Safety 3 2 1 Presentation of safety information ...

Страница 3: ... operated by people including children with limited physical sensory or mental capacities or by people with insufficient experience or previ ous knowledge 2 4 Foreseeable misuse The following is considered to be foreseeable misuse Operating the Isomix F beyond its specifications Improper use of the Isomix F Modifications to the Isomix F that have not been agreed with the manufacturer Use of replac...

Страница 4: ... circuit and thus keeps the flow tem perature constant within a narrow range The actual value can be checked on the thermometer 5 Check valve 6 pre vents a short circuit of the primary circuit The temperature limiter 8 switches off the circulating pump 1 when the supply temperature is exceeded thus prevent ing the panel heating system from overheating 5 Technical data Hydraulic performance data Ma...

Страница 5: ...no 10070292 5 EN ENGLISH 6 Overall dimensions G1 G1 22 5 82 ca 225 ca 98 210 65 5 25 1 Fl 1 Fl Fig 6 1 Overall dimension 7 Pressure loss diagram 1 10 100 1 000 100 1 000 10 000 Fig 7 1 Pressure loss diagram Flow rate l h Pressure loss mbar ...

Страница 6: ...own before carrying out maintenance cleaning and repair work During installation it must be ensured that the cables from the pump and temperature limiter are not damaged or kinked the sensor capillary tube is not damaged or kinked The cables must not be under tension 1 Fit the control station to the manifold with the 1 nuts and associated seals The control station can be fitted on the right or lef...

Страница 7: ...tion of flow until the air and any contamination has been removed from the circuit completely The non return valve 14 in the mixer bypass prevents any short circuit when flushing 10 Repeat the process for all the heating circuits Fig 8 3 Fig 8 4 NOTICE Flushing is permitted only in the direction of flow of the heating circuits i e the water must enter through the flow manifold and come out of the ...

Страница 8: ...open Hot water is injected from the primary heating circuit As a result the control station heats up When the maxi mum temperature of the TL is reached the contact opens The pump does not switch on again Remove TL from the control station and fit to supply heat ing circuit manifold See 1 1 2 Underfloor heating flow temperature cannot be set to the required value or the feed temperature fluctuates ...

Страница 9: ...e seals as required 2 Functional check Check that settings and operating and performance parameters are set correctly Check flow noise during operation Ask users if there are any noticeable problems 3 Action to be taken following maintenance work Check that all screw fittings that were unscrewed have been retightened and retighten if necessary Remove all tools materials and other equipment used fr...

Страница 10: ...omix F properly or commission a spe cialist company to do so 3 Sort the assemblies and component parts into recyclable materials hazardous substances and operating materials 4 Dispose of the assemblies and components in accord ance with local laws and regulations or take them to be recycled 11 1Return to the manufacturer Get in contact with the manufacturer if you would like to return the Isomix F...

Отзывы: