manualshive.com logo in svg
background image

ISOMIX F-IM-DE-W-UK-01-2021-Rev4 | Part no. 10070292

3

EN

ENGLISH

2  Safety

2.1  Presentation of safety information

DANGER

DANGER indicates an imminent danger

that may cause serious physical injury or death if the 
appropriate safety precautions are not in place.

!

 

WARNING

WARNING indicates a danger arising

through incorrect behavior (e.g. misuse, disregarding 
notices, etc.) that may cause serious physical injury or 
death.

!

 

CAUTION

CAUTION indicates a potentially

dangerous situation that may cause minor or slight 
injuries if the appropriate safety precautions are not in 
place.

NOTICE

NOTE indicates a situation that may

cause material damage if the corresponding precau-
tions are not taken.

2.2  Important safety information

•  Before using the Isomix-F, read this operating manual 

through carefully.

•  Connect the Isomix-F only to a power source that corre-

sponds to the mains voltage specified on the rating plate of 
the Isomix-F.

•  The power supply to the Isomix-F must be disconnected 

prior to maintenance, cleaning and repair work.

•  Maintenance, cleaning and repair work may be carried out 

by trained specialist personnel only.

•  The Isomix-F must not be used if it is damaged or is no 

longer operating correctly. In this case, contact your spe-
cialist dealer immediately.

•  Observe the maintenance instructions and intervals.

•  Protect the Isomix-F from the weather.

•  Never use the Isomix-F outdoors.

•  The unit may be used only in accordance with its intend-

ed use.

2.3  Intended use

The control station Isomix-F is used for constant mainte-
nance of the flow temperature in surface heating systems. 
The control station is intended for use in dry rooms in resi-
dential or commercial areas. It is usually installed in the heat-
ing room or in a distribution cabinet.

The Isomix-F is not intended to be operated by people 
(including children) with limited physical, sensory or mental 
capacities, or by people with insufficient experience or previ-
ous knowledge.

2.4  Foreseeable misuse

The following is considered to be foreseeable misuse:

•  Operating the Isomix-F beyond its specifications.

•  Improper use of the Isomix-F.

•  Modifications to the Isomix-F that have not been agreed 

with the manufacturer.

•  Use of replacement or wear parts that have not been 

approved by the manufacturer.

•  Operating the Isomix-F outdoors.

2.5  Responsibilities of the plant operator

The plant operator must ensure that:

•  the Isomix-F is used only for its intended purpose

•  the Isomix-F is installed, operated and maintained accord-

ing to the specifications of the installation and operating 
manual

•  the Isomix-F is operated only in accordance with local reg-

ulations and occupational health and safety regulations

•  all precautionary measures have been taken to avoid dan-

gers originating from the Isomix-F

•  all precautions for first aid and firefighting have been taken

•  only authorized and trained users have access to the 

Isomix-F and operate it

•  users have access to this installation and operating manual 

at all times

2.6  Personnel groups

Only qualified persons may install and operate the Isomix-F 
and carry out maintenance work.

Operators

Operators are deemed to be qualified if they have read these 
operating instructions and understood the potential hazards 
associated with improper behavior.

Fitters/commissioning engineers

Fitters/commissioning engineers are in a position to carry out 
work on the Isomix-F, taking into consideration the applicable 
standards, provisions, regulations and laws and their tech-
nical training and technical knowledge, and can detect and 
prevent potential hazards.

2.7  Information on the operating environment

Corrosion and chemical and physical reactions can damage 
the control station.

The system planner is responsible for evaluating these 
parameters and developing remedies�

Содержание Isomix-F

Страница 1: ...Isomix F Control station for constant maintenance of the flow temperature in surface heating systems Installation and Operating Manual translated from the original operating manual WattsWater eu ...

Страница 2: ...cording to Machinery Directive 2006 42 EC has been issued for the Isomix F product 1 3 Product features All connections to the system have 1 male thread and flat sealing Very convenient controls compact space saving design Contents 1 General information 2 1 1 Important information about this manual 2 1 2 Product conformity 2 1 3 Product features 2 2 Safety 3 2 1 Presentation of safety information ...

Страница 3: ... operated by people including children with limited physical sensory or mental capacities or by people with insufficient experience or previ ous knowledge 2 4 Foreseeable misuse The following is considered to be foreseeable misuse Operating the Isomix F beyond its specifications Improper use of the Isomix F Modifications to the Isomix F that have not been agreed with the manufacturer Use of replac...

Страница 4: ... circuit and thus keeps the flow tem perature constant within a narrow range The actual value can be checked on the thermometer 5 Check valve 6 pre vents a short circuit of the primary circuit The temperature limiter 8 switches off the circulating pump 1 when the supply temperature is exceeded thus prevent ing the panel heating system from overheating 5 Technical data Hydraulic performance data Ma...

Страница 5: ...no 10070292 5 EN ENGLISH 6 Overall dimensions G1 G1 22 5 82 ca 225 ca 98 210 65 5 25 1 Fl 1 Fl Fig 6 1 Overall dimension 7 Pressure loss diagram 1 10 100 1 000 100 1 000 10 000 Fig 7 1 Pressure loss diagram Flow rate l h Pressure loss mbar ...

Страница 6: ...own before carrying out maintenance cleaning and repair work During installation it must be ensured that the cables from the pump and temperature limiter are not damaged or kinked the sensor capillary tube is not damaged or kinked The cables must not be under tension 1 Fit the control station to the manifold with the 1 nuts and associated seals The control station can be fitted on the right or lef...

Страница 7: ...tion of flow until the air and any contamination has been removed from the circuit completely The non return valve 14 in the mixer bypass prevents any short circuit when flushing 10 Repeat the process for all the heating circuits Fig 8 3 Fig 8 4 NOTICE Flushing is permitted only in the direction of flow of the heating circuits i e the water must enter through the flow manifold and come out of the ...

Страница 8: ...open Hot water is injected from the primary heating circuit As a result the control station heats up When the maxi mum temperature of the TL is reached the contact opens The pump does not switch on again Remove TL from the control station and fit to supply heat ing circuit manifold See 1 1 2 Underfloor heating flow temperature cannot be set to the required value or the feed temperature fluctuates ...

Страница 9: ...e seals as required 2 Functional check Check that settings and operating and performance parameters are set correctly Check flow noise during operation Ask users if there are any noticeable problems 3 Action to be taken following maintenance work Check that all screw fittings that were unscrewed have been retightened and retighten if necessary Remove all tools materials and other equipment used fr...

Страница 10: ...omix F properly or commission a spe cialist company to do so 3 Sort the assemblies and component parts into recyclable materials hazardous substances and operating materials 4 Dispose of the assemblies and components in accord ance with local laws and regulations or take them to be recycled 11 1Return to the manufacturer Get in contact with the manufacturer if you would like to return the Isomix F...