Draw-off point protection
The fitting of anti-scald cartridges is MANDATORY at the draw-off points
to protect
users from the risk of scalding if the system is accidentally used during a thermal shock
cycle. Water is cut off if the temperature exceeds 48 °C.
Anti-scald cartridge specifications:
max. static pressure: 10 bar; max. dynamic
pressure: 5 bar; cut-off temperature: between 48 and 50 °C; KV: 1.3 at 42 °C. Observe
the water flow direction indicated by the arrow marked on the device.
Anti-scald cartridge for shower
Anti-scald cartridge for washbasin
Anti-scald cartridges
Description
Part number
Anti-scald cartridge M/F 1/2" (shower)
2297155
Anti-scald cartridge M 24x1 with aerator (washbasin)
2297156
What is legionella?
Legionella bacteria (which cause legionellosis) are found naturally in water and pose
an
extremely dangerous risk to public health
. Transmission occurs through inhalation. These
bacteria multiply when the hot water temperature is too low or water stagnates inside the
system, or due to a build-up of sediment and scale in the pipes.
The bacteria are destroyed
when the water temperature reaches 60 °C
(and taking around 30 minutes).
LEGIONELLA
UK
ENGLISH
Electrical connection
ALARM
NC
NO
Circulation pump relay: 10 A/250 VAC (NO)
FLUSH
VA
LV
E
L
N
Flush valve wiring diagram
(circuit without recirculation loop)
Timer (if present)
CIRCUL
AT
ION PUMP
L
N
FLUSH
VA
LV
E
L
N
Circulation pump wiring diagram
(circuit with a recirculation loop)
Domestic hot water
production
wiring diagram
Flush valve wiring diagram
(circuit with recirculation loop)
Electric alarm (standard)
wiring diagram
Hot water
production
relay:
10 A/250 VAC (NO)
DHW PRODUCTION SYSTE
M
Hot water production
relay wiring is necessary
to send temperature
data to the DHW system.
A
E
B
C
D
ModBus connection wiring diagram
F
Circulation pump relay: 10 A/250 VAC (NO)
Flush relay: 10 A/250 VAC (NO)
Relay: 8 A/250 VAC (NO/NC)
OV
AB
OV
Optional
A
B
Terminal block
Network
15
ENGLISH
EN