III - OPERATING PRINCIPLES
Functions
The e-ULTRAMIX
®
system provides various functions to enable effective management
and maintenance of your DHW system.
•
Mixed water distribution:
The e-ULTRAMIX
®
ensures the mixed water supply tempera-
ture remains constant whatever the flow rate or pressure variations in the system. It thus
guarantees safety by maintaining an appropriate and safe temperature. Via the electric
actuator, the control unit transmits the setpoint temperature to be supplied by the
thermostatic mixing valve using the probe placed on the mixed water outlet. The tempe-
rature of mixed water supplied is displayed on the control unit screen. The setpoint
temperature for mixed water can be configured (via the control unit) in increments of 1°C.
•
Preventive heat treatment:
the integrated timer in the e-ULTRAMIX
®
control unit is used
to program thermal treatment cycles on the system, displayed as “Thermal shock” on
the screens. Thermal treatment involves increasing the water temperature to a certain
value for a fixed period. The return probe measures the temperature reached in all or part
of the network, and can be installed at a suitable point in the recirculation loop.
•
Flush
(depending on your system): this cycle is initiated automatically after the thermal
shock cycle and returns the water temperature quickly to its normal values. It can also
be programmed to drain any residue from the mixed water production system.