Benchmark 750 – 1000 Boiler User Manual - INTERNATIONAL
CHAPTER 3 – OPERATION
Page
44
of
170
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0119_0A
11/03/2016
Ph.: 800-526-0288
GF-130-I
Table 3-4: Configuration Menu
Menu Item Display
Available Choices or Limits
Default
Minimum
Maximum
21
Setpt Limit Band
0°F (0
°
C)
10°F (5.5
°
C)
5°F (2.75
°
C)
22
Network Timeout
5 sec.
999 sec.
30 sec.
23
Shutoff Dly Temp
0°F (0
°
C)
25°F (13.75
°
C)
10°F (5.5
°
C)
24
Demand Offset
0°F (0
°
C)
25°F (13.75
°
C)
0°F (0
°
C)
25
Deadband High
0°F (0
°
C)
25°F (13.75
°
C)
5°F (2.75
°
C)
26
Deadband Low
0°F (0
°
C)
25°F (13.75
°
C)
5°F (2.75
°
C)
27
IGST Version
V2.00 or Lower
V2.02
28
IGN Time Setting
4 sec.
7 sec.
29
Slow Shutdown
Enabled or Disabled
Disabled
30
Slow Sht Duration
0 sec.
9,999 sec.
60 sec.
31
Slow Sht Threshold
40%
100%
60%
32
BST Menu
Enabled or Disabled
Disabled
*NOTE
The
Bldg Ref Temp
and
Reset Ratio
menu Items are only
displayed when the
Outdoor Sensor
menu item is set to
Enabled
.
--CAUTION -
DO NOT
change
the
Analog Output
menu item from its default
setting (Valve Position 0-10V).