Benchmark 750 – 1000 Boiler User Manual - INTERNATIONAL
CHAPTER 3 – OPERATION
OMM-0119_0A
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
Page
47
of
170
GF-130-I
Ph.: 800-526-0288
11/03
/2016
Table 3-7: BST Menu
Menu Item Display
Available Choices or Limits
Default
Minimum
Maximum
16
Header Temp Point
0
255
14
17
BST Outdoor Sens
Disabled
Enabled
Disabled
18
Outdr Tmp Source
Outdoor Temp
Network
Outdoor Temp
19
Outdoor Tmp Addr
0
255
240
20
Outdoor Tmp Pnt
0
255
215
21
BST Remote Signal
4-20 mA/1-5 VDC;
0-20 mA/0-
5 VDC;
Network
Network
22
BST Auto Mstr
No
Yes
NOTE! A Modbus
temperature transmitter
must be installed in
conjunction with this
feature.
No
23
BST Auto Timer
10 sec
120 sec
30 sec
24
Remote Intlk Use
Heating Boiler
Shutdown
System Shutdown
System Shutdown
25
One Boiler Mode
Off
On-Outlet
Temp
On-Avg Temp
Off
26
1 Blr Threshold
10
35
25
27
Setpoint Setback
Disable
Enable
Disable
28
Setback Setpoint
BST Setpt Lo Limit
BST Setpt HI Limit
130°F (54.4°C)
29
Setback Start
12:00am
11:59pm
12.00am
30
Setback End
12:00am
11:59pm
12.00am
31
Rate Threshold
1°F (0.55°C)
30°F (16.5°C)
15°F (8.25°C)
32
*BST OPERATE MENU*
Disabled
Enabled
Disabled
33
BST Next On VP
16%
100%
50%
34
BST Max Boilers
1
8
8
35
BST On Delay
30 sec
300 sec
60 sec
36
BST On Timeout
15 sec
300 sec
60 Sec
37
Valve Override
Off
Closed
Open
Off
38
Valve Off Delay
0
15 min
1 min
39
BST Sequencing
Run Hours
Unit Size
Select Lead
Run Hours
40
Select Lead Unit
0
127
0
41
Select Lag Unit
0
127
0
42
Lead/Lag Hours
25 hours
225 hours
72 hours
43
*BST TEMP CTRL MENU*
Disabled
Enabled
Disabled