49
Converter
’
s connections
N.B. : Using a cable that is less than 3 x 1.5 mm
2
in diameter will affect both the
output and the performance of the hydrogenerator.
The GND position must not be connected (ground terminal).
N.B. : The phase sequence is irrelevant. Therefore, there is no need to take into
account the color or numbering of the cables.
Using a solar panel
The converter has 2 inputs : one for the hydrogenerator and one for the solar panel. The solar
panel's maximum voltage must not exceed 50 VCC and the intensity must not exceed 14 amps.
Minimum voltage to start producing with the solar panels is 7,5VCC.
Wire the solar panel using the 2
nd
premounted plug CA
-
03, taking care of the polarity:
NEGATIVE SOLAR: BLACK
POSITIVE SOLAR: RED
WARNING : RESPECT THE POLARITY OF THE SOLAR PANEL
not used /
non utilisé
(female contact /
contact femelle
)
(female contact /
contact femelle
)
(female contact /
contact femelle
)
(male contact /
contact mâle
)
not used /
non utilisé
heat shrinking tube
heat shrinking tube
HYDROGENERATOR CONNECTOR
Phases : RED, ORANGE, BROWN
(Rouge, Orange, Marron)
Not used : BLACK
(Noir non utilisé)
SOLAR CONNECTOR
Positive : RED max 50V in open circuit
(Rouge, max 50V)
Negative : BLACK common with battery negative
(Noir)
Not used : ORANGE, BROWN
(Orange, Marron non utilisés)
BATT #1 POSITIVE
POSITIF BATTERIE N °1
BATT #2 POSITIVE
POSITIF BATTERIE N °2
COMMON BATT NEGATIVE
NEGATIF COMMUN
–