23
Remark: If Fn_61 = 6 - 11, Terminals 10/11 are normally opened during power off, and normally closed
during power on.
Fn_10 : Control mode select = 0 : Digital operator control
= 1 : Remote control (terminal stop)
STOP key can be used for emergency stop during Remote control(Fn_10 =1). (Refer to Fn_48)
Fn_11 : Frequency command method select
= 0 : Run by Fn _25
= 1 : Run by VR on digital operator
=
2
:
Run
by
VR
on
TM2(terminal
12-14)
=
3
:
Run
by
multi-function
input
freq.
command
(terminal
6-8)
1. When Fn_11=1, Fn_56 - Fn_58 = 15
Frequency is set by VR on digital operator if multi-function input is OFF ; Frequency is set by
VR on terminal block (TM2) or other analog signals if multi-function input is ON.
2. When Fn_11=2, Fn_56 - Fn_58 = 15
Frequency is set by VR on terminal block (TM2) or other analog signals if multi-function input
is OFF; Frequency is set by VR on digital operator if multi-function is ON.
3. Please refer to Fn_56 - Fn_58 for UP/DOWN terminals.
Remark 1 : Frequency will be controlled by multi-speed setting when jog or multi-speed
are engaged. keys on digital operator and up/down control of TM2 will
be ineffective as long as multi-speed is ON. Frequency will be back to preset
value
after multi-speed is OFF.
Remark 2 : keys and up/down control of TM2 will also be ineffective when
Accel.\Decel during run mode or during the period of switching multi-speed.
Stall prevention during Accel./Decel./Running.
Fn_12: xxx0 : Stall prevention during accel. enable
xxx1 : Stall prevention during accel. disable
xx0x : Stall prevention during decel. enable
xx1x : Stall prevention during decel. disable
x0xx : Stall prevention during running. enable
x1xx : Stall prevention during running. disable
0xxx : Stall prevention decel. time set by Fn_02.
1xxx : Stall prevention decel. time set by Fn_15.