26
Analog frequency signal control
Fn_26 : Frequency reference
: 0.0 - 400Hz
Fn_27 : Voltage reference ratio 1
: 0.0 - 100%
Fn_28 : Voltage reference ratio 2
: 0.0 - 999.9%
Fn_29 : Positive /Negative direction : 0: Positive
1: Negative
Fn_06
100%
1
2
3
Fn_27
Fn_28
1
2
Fn_26
Internal
signal
Fn_06
100%
Fn_27
Fn_28
Fn_26
Internal
signal
4
6
5
Hz
Hz
% of frequency setting signal
% of frequency setting signal
Fn_26 Fn_27 Fn_28 Fn_29
curve 1
set freq.
set 0
set %
0
curve 2
set 0
set 0
set %
0
curve 3
set 0
set %
set %
0
curve 4
set freq.
set 0
set %
1
curve 5
set 0
set 0
set %
1
curve 6
set 0
set %
set %
1
1.
Fn_26/27/28/29 will be effective only when Fn_11 = 1 or 2 ( frequency set by digital
operator r terminal analog frequency signal control)
2.
Fn_27 can be set as follows (curve 3) :
a: If signal is 1~ 5 V, Fn_27 will equal to the voltage of 0Hz divided by 5V
b: If signal is 4 ~ 20 mA, Fn_27 will equal to the current of 0Hz divided by 20 mA.
c: If signal is 0~ 10V, same method as above
3.
Setting of Fn_28: If signal is 0~ 20 mA, Fn_28 will equal to the current of Fn_06
divided by 20 mA.
Remark: Signals of VR on TM2 and Digital operator are 0~5V; Analog input terminal of
terminal block can accept 0~5 V / 0~10V/ 0~20 mA signals.
Remark: Fn_28 must be greater than Fn_27