66 MLS User’s Guide
Setup
Controller Address
Use this menu to set the MLS controller address. The controller address
is used for multiple controller communications on a single RS-485
cable, so each MLS must have a different address. Begin with address 1
for the first controller and assign each subsequent controller the next
higher address.
Selectable Range:
a number between 1 and 32.
Communications Error Checking
Use this menu to set the data check algorithm used in the ANAFAZE
communications protocol to Block Check Character (BCC) or to Cyclic
Redundancy Check (CRC).
CRC is a more secure error checking algorithm than BCC, but it
requires more calculation time and slows the MLS communications.
BCC ensures a high degree of communications integrity, so ANAFAZE
recommends that you use BCC unless your application specifically
requires CRC.
Selectable values:
BCC or CRC.
NOTE
If you are using ANASOFT, be sure to configure
ANAINSTL for the same error checking method that
you set in this menu.
LOOP PROCESS UNITS
ALARM SETPOINT STATUS OUT%
CONTROLLER
ADDRESS? 1
LOOP PROCESS UNITS
ALARM SETPOINT STATUS OUT%
COMMUNICATIONS
ERR CHECK? BCC
Содержание MLS-PM
Страница 13: ...Contents MLS User s Guide vi...
Страница 17: ...4 MLS User s Guide Overview...
Страница 59: ...46 MLS User s Guide Installation...
Страница 120: ...Tuning and Control MLS User s Guide 107...
Страница 121: ...108 MLS User s Guide Tuning and Control...
Страница 131: ...118 MLS User s Guide Troubleshooting...
Страница 143: ...Glossary MLS User s Guide 130...