70 MLS User’s Guide
Setup
Input Type
Use this menu to configure the input sensor for each loop as one of these
input types:
•
Thermocouple types (J, K, T, S, R and B).
•
RTD. Three ranges: RTD1 (Platinum Class A), RTD2 (Platinum
Class B), and RTD3 (Nickel).
•
Linear and Pulse inputs.
•
Skip (an input type available for unused channels.) The scanning dis-
play doesn't show loops you've set to Skip.
The next table shows the MLS' input types and ranges.
Input
Type
Fahrenheit
Range
Celsius Range
J
-350 to +1400
-212 to +760
K
-450 to +2500
-268 to +1371
T
-450 to +750
-268 to +399
S
0 to +3200
-18 to +1760
R
0 to +3210
-18 to +1766
B
+150 to +3200
+66 to +1760
RTD1
-148.0 to +572.0
-100.0 to +300.0
RTD2
-184 to +1544
-120 to +840
RTD3
-94 to 572
-70 to 300
Pulse
0-2 KHz
Skip
Loop is not scanned or displayed.
Linear
see the
Linear Scaling section
(this chap-
ter) and
Appendix
.
LOOP PROCESS UNITS
ALARM SETPOINT STATUS OUT%
06 INPUT TYPE?
J T/C