8 MLS User’s Guide
Introduction
RTD Ranges
Miscellaneous Specifications
Analog Outputs
Digital Inputs
RTD1
-148.0 to 572
°
F (-100.0 to 300.0
°
C)
0.1
°
C
RTD2
-184 to 1544
°
F (-120 to 840
°
C)
1.0
°
C
RTD3
-94 to 572
°
F (-70 to 300
°
C)
1.0
°
C
T/C break detection
Pulse type for upscale break detection and
thermocouple alarm display.
Milliamp inputs
0-10 mA, 0-20 mA (4-20 mA), etc., with scal-
ing resistors.
Infrared inputs
power supply included, with scaling resistors
for IRSM.
Source impedance
Measurements are within specification with
up to 500 ohms source resistance.
The Watlow-Anafaze Digital to Analog Converter (DAC) is an optional
module for MLS and CLS controllers. It lets you convert a distributed zero
crossing output signal to an analog process control signal. You can purchase
4-20 mAdc, 0-5 Vdc, and 0-10 Vdc versions of the DAC.
Watlow-Anafaze also offers the Serial DAC for precision open-loop con-
trol. 0-5 Vdc / 4-20 mAdc jumper selectable. Contact Watlow-Anafaze for
more information about the DAC and Serial DAC.
Number
8
Input voltage protection
Diodes to supply and common
Absolute maximum input
current
+10 mA
Voltage levels
<1.3V=Low; >3.7V=High
Maximum input current
1.2 mA from MLS with input at zero volts
Maximum switch resis-
tance to pull input low
1 Kohm
Minimum switch off resis-
tance
11 Kohm
Содержание MLS-PM
Страница 13: ...Contents MLS User s Guide vi...
Страница 17: ...4 MLS User s Guide Overview...
Страница 59: ...46 MLS User s Guide Installation...
Страница 120: ...Tuning and Control MLS User s Guide 107...
Страница 121: ...108 MLS User s Guide Tuning and Control...
Страница 131: ...118 MLS User s Guide Troubleshooting...
Страница 143: ...Glossary MLS User s Guide 130...