32
Installation & Operation Manual
Copyright © Puretec Pty Ltd 2022
Problem
Ref.
Possible Cause
Solution
6. Control valve regenerates
at wrong time of day.
a.
Power outage.
Reset time of day. The CR2032
battery may need to be replaced.
b.
Time of day not set correctly.
Reset to correct time of day.
c.
Time of regeneration set incorrectly.
Reset regeneration time.
d.
Control valve set at ”on 0”
(immediate regeneration).
Check programming setting and
reset to NORMAL (for a delayed
regen time).
e.
Control valve set at ” on
0” (delayed and/ or immediate).
Check programming setting and
reset to NORMAL (for a delayed
regen time).
7. Control valve does not
regenerate
automatically but
does
when the REGEN button is
depressed and held.
a.
Bypass valve in bypass position.
Turn bypass handles to place bypass
in service position.
b.
Meter is not connected to meter
connection on PC board.
Connect meter to three pin
connection labelled METER on PC
board.
c.
Restricted/stalled meter turbine.
Remove meter and check for
rotation or foreign material.
d.
Incorrect programming.
Check for programming error.
e.
Meter wire not installed securely
into three pin
connector.
Verify meter cable wires are
installed securely into three pin
connector labelled METER.
f.
Defective meter.
Replace meter.
g.
Defective PC board.
Replace PC board.
8. Excessive water in
regenerant tank.
Improper program settings.
Check refill setting.
Plugged injector.
Remove injector and clean or
replace.
Drive cap assembly not tightened
in properly.
Re-tighten the drive cap assembly.
Damaged seal/stack assembly.
Replace seal/stack.
Restricted or kinked drain line.
Check drain line for restrictions or
debris and or un-kink drain line.
Plugged backwash flow controller.
Remove backwash flow controller
and clean or replace.
Missing refill flow controller.
Replace refill flow controller.
Troubleshooting