Copyright © Puretec Pty Ltd 2022
SOL-2CI Commercial Series User Guide
Setup Programming
16.
Set Relay 2 Deactivate Time
using ▲ or ▼.
• If "on" is selected in step 14 the relay will deactivate
after the time set has expired. Ranges from 1 second to
200 minutes. To activate the relay during regeneration,
program the deactivate time to 72:00.
• If "L on" or "L softening regen on" is selected in step 14
the relay will deactivate after the time set has expired
or after the meter stops registering flow, whichever
comes first. Ranges from 1 second to 20 minutes.
Press "NEXT" to exit Setup Programming.
Installer Display Settings
Note:
Press "REGEN" at any time to return to previous step.
1. Press "NEXT" and ▲ simultaneously for 3 seconds.
2.
Hardness:
Set the amount of influent hardness using ▼ or
▲. Units are ppm, which is equal to mg / L.
0 - 100 ppm - Adjustable in increments of 1 ppm.
100 + ppm - Adjustable in increments of 10 ppm.
Press "NEXT" to go to the next step.
3.
Service Water Hardness:
Preset to default (0 ppm).
Changing this value will not alter the outlet hardness.
Press "NEXT" to go to the next step.
4.
Day Override:
Preset to default (28 days). Set Day Override
using ▲ or ▼. Adjustments are in increments of 10 ppm
(always round-up to nearest ppm).
• Number of days between regeneration (1 to 28); or
• oFF
When volume capacity set to "oFF" or to a number, sets the
number of days between regenerations. If volume is set to
AUTO a regeneration initiation will be called for on that day
even if sufficient volume of water were not used to call for
regeneration.
RETURN TO NORMAL MODE